2020-10-15 11:03:19 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. REVISION: 20100534 |
| W. P. B. PERMIT: 20050704 |
| ADD: 501 S. FLAGLER DR. 2ND FLOOR COMMON AREA/ ELEVATOR |
| LOBBY AREA |
| CONT: ANDERSON MOORE CONSTRUCTION |
| TEL: 561-753-7400 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. OCT. 15TH/ 2020 |
| ACTION: BUILDING PROVISO |
| |
| 1) SHEET A1.1.2 & A2.1.1. BOTH SHOW NEW DECORATIVE WALL |
| SCONCES MOUNTED @ 5 FEET ABOVE FINISH FLOOR. THE PLAN |
| DOES NOT PROVIDE THE TOTAL DISTANCE THE WALL SCONCES |
| STAND OFF THE WALL. MUST SHOW COMPLIANCE WITH THE 2017 |
| ACCESSIBILITY CODE SECTION PROTRUDING OBJECTS 307.2 |
| PROTRUSION LIMITS 307.2. OBJECTS WITH LEADING EDGES |
| MORE THAN 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE |
| THE FLOOR SHALL NOT PROTRUDE MORE THAN 4 INCHES |
| HORIZONTALLY INTO THE CIRCULATION PATH. |
| |