Plan Review Notes For Permit 20100518 |
Permit Number |
20100518 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-10-27 10:16:06 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) PROVIDE THE WIND LOAD DESIGN DATA ON THE PLANS. FBC | | 1609 | | | | 2) SUBMIT SIGNED AND SEALED CALCULATIONS FOR SIGN | | ANCHORING REQUIREMENTS FROM A FLORIDA LICENSED | | ENGINEER. FBC 3107 & FS 471 | | | | 3) THE VALUE FOR THIS SIGN APPEARS TO BE TOO LOW. | | SUBMIT A COPY OF THE CONTRACT TO VERIFY THE COST OF THE | | SIGN, INSTALLATION, DESIGN, ENGINEERING, LABOR, | | MATERIAL, OVERHEAD AND PROFIT. FBC 109.3 | | | | 4) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | CITY RE-SUBMITTAL FORM. |
|