Plan Review Notes For Permit 20100498 |
Permit Number |
20100498 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-10-16 09:08:07 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | FBC B 107.2.1: | | | | 1) THE COVER PAGE A0.0 & DEMO PLAN PAGE A0.3, INDICATE | | THAT THIS PLAN COVERS STAIR DEMO WORK WITH A NOTE | | REFERRING TO SEPARATE PERMITS FOR STAIRS. THE OTHER | | PERMIT APPLICATIONS, (# 19061180 & 20100658), THAT | | INCLUDE STAIR DEMOLITION WORK HAVE NOT BEEN APPROVED. | | PLEASE REMOVE STAIRS FROM THE WORK AREAS ON THIS PLAN | | (PAGES A0.0 & A0.3). | | | | 2) IF THE INTENT IS TO INCLUDE STAIR DEMOLITION ON THIS | | PLAN TO BE USED IN CONJUNCTION WITH THE OTHER PERMITS, | | 20100658 WILL HAVE TO BE APPROVED AND 19061180 WILL | | HAVE TO BE CLOSED. IN ANY CASE THE THRESHOLD/SPECIAL | | INSPECTOR AGREEMENT NEEDS TO BE COMPLETED TO INCLUDE | | THE CONTRACTOR(FAST TRAC) IN THE AGREEMENT. | | | | 3) A PROCEDURE SHOWING HOW THE PATRONS OF THE BUILDING | | WILL BE DIRECTED TO AN ALTERNATE EGRESS WHILE THE STAIR | | DEMOLITION AND WORK IS TAKING PLACE IS REQUIRED. |
|