 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1:
  
 1) THE COVER PAGE A0.0 & DEMO PLAN PAGE A0.3, INDICATE
 THAT THIS PLAN COVERS STAIR DEMO WORK WITH A NOTE
 REFERRING TO SEPARATE PERMITS FOR STAIRS. THE OTHER
 PERMIT APPLICATIONS, (# 19061180 & 20100658), THAT
 INCLUDE STAIR DEMOLITION WORK HAVE NOT BEEN APPROVED.
 PLEASE REMOVE STAIRS FROM THE WORK AREAS ON THIS PLAN
 (PAGES A0.0 & A0.3).
  
 2) IF THE INTENT IS TO INCLUDE STAIR DEMOLITION ON THIS
 PLAN TO BE USED IN CONJUNCTION WITH THE OTHER PERMITS,
 20100658 WILL HAVE TO BE APPROVED AND 19061180 WILL
 HAVE TO BE CLOSED. IN ANY CASE THE THRESHOLD/SPECIAL
 INSPECTOR AGREEMENT NEEDS TO BE COMPLETED TO INCLUDE
 THE CONTRACTOR(FAST TRAC) IN THE AGREEMENT.
  
 3) A PROCEDURE SHOWING HOW THE PATRONS OF THE BUILDING
 WILL BE DIRECTED TO AN ALTERNATE EGRESS WHILE THE STAIR
 DEMOLITION AND WORK IS TAKING PLACE IS REQUIRED.