2020-10-27 09:28:03PLAN REVIEW GENERATOR / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: PRE-CAST GENERATOR PAD ENGINEERING AND GENERATOR
 SPEC?S.
  
 1. THE GENERATOR SPECIFICATIONS SUBMITTED FOR REVIEW
 ARE FOR A 2016 MODEL GENERAC 38KW GENERATOR. PROVIDE
 THE CURRENT SPECIFICATIONS FOR THE PROPOSED 38KW
 GENERATOR.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
  
 2.THE MINIMUM WEIGHT OF THE PROPOSED GENERATOR ON TABLE
 2.2 OF THE GENERATOR PAD ENGINEERING IS 1235 LBS. THE
 WEIGHT OF THE PROPOSED GENERATOR IS 560 LBS.
 PLEASE CLARIFY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
  
  