2020-12-01 07:48:471ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100483
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IT APPEARS THAT THE NEW HOOD WILL BE INSTALLED IN
 THE LOCATION OF THE CURRENT RTU RETURN DUCT. PLEASE
 PROVIDE A DRAWING WITH THE EXISTING DUCT WORK LAYOUT
 AND THE HOOD. THIS MAY REQUIRE A MECHANICAL PERMIT IF
 ANY DUCTWORK IS REMOVED OR MOVED TO ALLOW THE
 INSTALLATION OF THE NEW HOOD, GREASE DUCT AND MAKEUP
 AIR. FBC 107.2.1
  
 2) MECHANICAL HOOD DRAWINGS SHEET 1 OF 5 MENTIONS THAT
 THE BUILDING HVAC SYSTEM SHALL PROVIDE MORE THAN 414
 CFM TO INSURE OVERALL BUILDING BALANCE IS POSITIVE.
 PLEASE OBTAIN A MECHANICAL PERMIT FOR THE ABOVE WORK
 AND PROVIDE MECHANICAL SHEETS WITH THAT PERMIT SHOWING
 THE AIR BALANCE, INCLUDING THE BATH EXHAUST FANS. FBC M
 508.1.2
  
 3) PLEASE PROVIDE THE SPECIFICATIONS FOR THE MUA AND
 SHOW THAT THE MAKE UP AIR TEMPERATURE DIFFERENCE DOES
 NOT EXCEED 10 DEG.F FBC M508.1.1
  
 4) PLEASE PROVIDE THE SPECIFICATIONS FOR THE COOKING
 EQUIPMENT LOCATED UNDER THE HOOD. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  