| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW STATUS: DENIED. |
| |
| 1) PLEASE PROVIDE ELECTRICAL DRAWINGS FOR THIS SPACE. |
| INCLUDE FLOOR LAYOUT INDICATING THE LOCATION OF NEW AND |
| EXISTING PANELS, LOCATION OF NEW EQUIPMENT, |
| DISCONNECTING MEANS, HOME RUNS TO PANELBOARDS AND ANY |
| OTHER NEW EQUIPMENT SUCH AS RECEPTACLES, AND LIGHTING |
| FIXTURES. |
| |
| 2) PLEASE PROVIDE A BASIC POWER RISER DIAGRAM |
| INDICATING ALL THE PANELBOARDS SERVING THIS TENANT-- |
| EITHER INSTALLED NEW OR EXISTING. INCLUDE RATINGS OF |
| PANELBOARDS, DISCONNECTING MEANS. INCLUDE THE SIZE AND |
| TYPES OF THE FEEDERS TO THESE PANELBOARDS, INCLUDING |
| SIZE AND TYPE OF CONDUITS, AND GROUND WIRES. |
| |
| 3) PLEASE PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR |
| ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE |
| CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE |
| TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, |
| 215.5, 408.4; FBC 107.3.5 |
| |
| 4) PLEASE PROVIDE LOAD CALCULATIONS FOR ALL PANELBOARDS |
| AFFECTED BY THIS PROJECT. INCLUDE NEW AND EXISTING |
| LOADS. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |