Plan Review Notes
Plan Review Notes For Permit 20100483
Permit Number 20100483
Review Stop AD
Sequence Number 1
Notes
Date Text
2020-10-30 09:14:18ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW STATUS: DENIED.
  
 1) PLEASE PROVIDE ELECTRICAL DRAWINGS FOR THIS SPACE.
 INCLUDE FLOOR LAYOUT INDICATING THE LOCATION OF NEW AND
 EXISTING PANELS, LOCATION OF NEW EQUIPMENT,
 DISCONNECTING MEANS, HOME RUNS TO PANELBOARDS AND ANY
 OTHER NEW EQUIPMENT SUCH AS RECEPTACLES, AND LIGHTING
 FIXTURES.
  
 2) PLEASE PROVIDE A BASIC POWER RISER DIAGRAM
 INDICATING ALL THE PANELBOARDS SERVING THIS TENANT--
 EITHER INSTALLED NEW OR EXISTING. INCLUDE RATINGS OF
 PANELBOARDS, DISCONNECTING MEANS. INCLUDE THE SIZE AND
 TYPES OF THE FEEDERS TO THESE PANELBOARDS, INCLUDING
 SIZE AND TYPE OF CONDUITS, AND GROUND WIRES.
  
 3) PLEASE PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4; FBC 107.3.5
  
 4) PLEASE PROVIDE LOAD CALCULATIONS FOR ALL PANELBOARDS
 AFFECTED BY THIS PROJECT. INCLUDE NEW AND EXISTING
 LOADS.
  
  
  
  
  
  
  
  
  
  
  
2020-10-14 13:10:39CHANGED FROM 1700 45TH ST # 1742 TO 1742 45TH ST