Date |
Text |
2020-12-11 14:29:50 | BUILD OUT |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected]. |
| CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| AMENDMENTS |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) (I MISSED THIS THE FIRST REVIEW) DOOR AT ACCESSIBLE |
| RESTROOM WIDTH 2/8 DOESN'T WORK FBC 404.2.3 CLEAR |
| WIDTH. DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 |
| INCHES (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS |
| WITH SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE |
| OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 |
| DEGREES. |
| 2) ACCESSIBLE RESTROOM FBC ACCESSIBILITY = MIRROR |
| HEIGHT SHOULD STATE TO THE "BOTTOM OF THE REFLECTION" |
| 603.3 - SHOW TOILET PAPER DISPENSER DISTANCE (7" TO 9" |
| TO THE CENTER OF THE DISPENSER) FROM TOILET 604.7 - |
| GRAB BAR HEIGHT SHOULD STATE MAX TO TOP OF THE GRAB BAR |
| 609.4 (DRAWING A2 ONE OF THE DETAILS SHOWS HEIGHT AT |
| 36" TO THE CENTER OF THE GRAB THIS DOES NOT COMPLY WITH |
| THE MAX. HEIGHT TO THE TOP OF THE GRAB BAR) - DOOR |
| CANNOT SWING INTO FIXTURE CLEAR FLOOR SPACE 603.2.3 |
| (EXCEPTION (2).WHERE THE TOILET ROOM OR BATHING ROOM IS |
| FOR INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING |
| WITH 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC |
| OF THE DOOR SWING, DOORS SHALL BE PERMITTED TO SWING |
| INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR |
| ANY FIXTURE.(SHOW THIS CLEAR FLOOR SPACE). |
| 3) STOREFRONT DRAWINGS FROM THOMAS TWOMEY P.E. UNABLE |
| TO DETERMINE IF SEALED BY THE ENGINEER - SIGNED AND |
| SEALED DRAWINGS IN PROJECTDOX NEED TO BE |
| DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. |
| DRAWINGS DO NOT SHOW IN "ADOBE READER" AS |
| DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR |
| ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR |
| DIGITAL SIGNATURE ? YOU CAN DROP OFF THE ORIGINAL |
| SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE FRONT DESK |
| IN THE BUILDING DEPT. AT THE CITY HALL. |
| |