Plan Review Notes
Plan Review Notes For Permit 20100464
Permit Number 20100464
Review Stop P
Sequence Number 1
Notes
Date Text
2020-10-19 14:55:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 PLEASE NOTE THAT PLANS FOR CLOSED MASTER PERMIT
 19070494 LOCATED IN CITY OF WEST PALM BEACH'S FILENET
 WORKPLACE SHOWS THE EXISTING SPACE INCLUSIVE OF
 ELECTRICAL, PLUMBING AND MECHANICAL. IT APPEARS ALL
 EXISTING PLUMBING AND PLUMBING FIXTURES SHOWN ON NEW
 TENANT SPACE HAVE BEEN APPROVED ON PAST PERMITS.
  
 1.IS THERE A CHANGE OF OCCUPANCY? ORIGINAL OCCUPANCY
 FROM CLOSED MASTER PERMIT 19070494 INDICATES OCCUPANCY
 WAS B-BUSINESS. PER WPB FBC 107.2.1, PLEASE CLARIFY
 OCCUPANCY CLASSIFICATION OF THE EXISTING SPACE AND
 PROVIDE THE OCCUPANCY CLASSIFICATION OF THE NEW TENANT
 SPACE. PROVIDE OCCUPANT LOAD.
  
 2. ORIGINAL OCCUPANCY ON LIFE SAFETY PLANS FROM CLOSED
 MASTER PERMIT 19070494 INDICATES THERE IS A SERVICE
 SINK REQUIRED AND PROVIDED; THEY SHOW A JANITOR'S
 CLOSET BETWEEN THE ELECTRICAL ROOM AND THE MEN'S
 RESTROOM, BUT THEY DON'T SHOW THE FIXTURE. PER WPB FBC
 107.2.1, PLEASE CONFIRM AND SHOW EXISTING ON THE PLAN.
  
 3.PER WPB FBC 107.2.1, PLEASE PROVIDE PLUMBING DRAWINGS
 PLAN VIEW AND SIZED RISER DIAGRAM FOR WATER SUPPLY AND
 SANITARY SHOWING THE NEW PLUMBING WORK PLUMBING WORK.
  
 4.PER FBC PL 607.1, PROVIDE HOT WATER TO NEW LAVATORY
 AND BAR SINK. PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL, SCHEDULE AND DETAIL
 THE FOR WATER HEATING DEVICE.
  
 5.PER FBC PL 416.5 AND 607.1.2, TEMPERED WATER SHALL BE
 SUPPLIED TO THE LAVATORY THROUGH A WATER TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 AND SHALL
 LIMIT THE TEMPERED WATER TO A MAXIMUM OF 110 DEGREES F.
  
 6.REGARDING THE SANITARY RISER DIAGRAM ON PLAN SHEET
 A-1, THE BAR SINK SHALL CONNECT DOWNSTREAM OF THE
 LAVATORY AND WATER CLOSET PER FBC PL 912.1.
  
 7. PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON
 THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW
 SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT
 AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION.
  
 8.PER WPB FBC 107.2.1, PROVIDE A PLUMBING FIXTURE
 CONNECTION SCHEDULE, PROVIDING WATER AND WASTE
 CONNECTION SIZES, MAXIMUM WATERFLOW/CONSUMPTION AND
 FIXTURE SPECIFICATIONS. SHOW COMPLIANCE WITH FBC PL
 TABLE 604.4 "'MAXIMUM FLOW RATES AND CONSUMPTION FOR
 PLUMBING FIXTURES AND FIXTURE FITTINGS"
  
 9. PROVIDE ALCOVE WALL FOR DRINKING FOUNTAIN TO COMPLY
 WITH PER FBC ACC 307.2 WHICH STATES OBJECTS WITH
 LEADING EDGES MORE THAN 27 INCHES (685 MM) AND NOT MORE
 THAN 80 INCHES (2030 MM) ABOVE THE FINISH FLOOR OR
 GROUND SHALL PROTRUDE 4 INCHES (100 MM) MAXIMUM
 HORIZONTALLY INTO THE CIRCULATION PATH.
  
 10.PER WPB FBC 107.2.1, IDENTIFY ALL NEW AND EXISTING
 ACCESSIBLE SPACES/ROOMS ON THE FLOOR PLAN INCLUDING THE
 LOUNGE AREA.
  
 11. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC
 ACC CHAPTERS 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS
 FOR NEW TOILET ROOM INDICATING THE FOLLOWING:
 A.THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2
 B.CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1
 C.THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 D.THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 E.FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET PER FBC ACC 604.6
 F.TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 G.THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER
 FBC ACC 604.4.
 H.PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT
 THE CENTER) OF THE GRIPPING SURFACE.
 I.LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
 J.UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2
 K.MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC 603.3.
 L.SHOW TURNING SPACE COMPLYING WITH FBC ACC 304.3.1 OR
 304.3.2.
 M.DOOR TO TOILET ROOM SWINGS INTO LAVATORY CLEAR FLOOR
 SPACE. PER WPB FBC 107.2.1, CLARIFY THAT IT DOES NOT
 ENCROACH ON CLEAR FLOOR SPACE.
 N.DOORS SHALL BE PERMITTED TO SWING INTO TURNING SPACES
 PER FBC ACC 304.4.
  
 END OF COMMENTS.
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED OR DIGITALLY SIGNED
 AND SEALED BY THE DESIGNER IN ACCORDANCE WITH FAC AND
 FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20100464 1921 S DIXIE HWY
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved