Plan Review Notes
Plan Review Notes For Permit 20100464
Permit Number 20100464
Review Stop B
Sequence Number 1
Notes
Date Text
2020-10-26 11:10:16BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE HOURLY FIRE RATING FOR THE WALLS.
 2) PLEASE SHOW THE CEILING HEIGHT.
 3) PLEASE SHOW THE NEW SPACE SQUARE FOOTAGE.
 4) PLEASE SHOW THE OCCUPANT LOAD FBC 1004
 5) PLEASE SHOW THE OCCUPANCY CLASSIFICATION FBC CHAPTER
 3
 6) PLEASE SHOW THE USE FOR EACH ROOM.
 7) PLEASE SHOW THE BUILDING CONSTRUCTION TYPE FBC
 CHAPTER 6
 8) THE ADDED EXTERIOR DOORS CANNOT SWING INTO THE
 PUBLIC RIGHT-OF-WAY FBC 3202.2 (PLEASE PROVIDE A SURVEY
 THAT SHOWS THAT THIS DOES NOT OCCUR).
 9) PLEASE PROVIDE THE FRONT PAGES FOR THE DOOR PRODUCT
 APPROVAL (FLORIDA STATE FRONT PAGES) FL18413.
 10) ACCESSIBLE RESTROOM FBC ACCESSIBILITY = MIRROR
 HEIGHT SHOULD STATE TO THE BOTTOM OF THE REFLECTION
 603.3 - SHOW TOILET PAPER DISPENSER DISTANCE FROM
 TOILET 604.7 - GRAB BAR HEIGHT SHOULD STATE MAX TO TOP
 OF GRAB BAR 609.4 - DOOR CANNOT SWING INTO FIXTURE
 CLEAR FLOOR SPACE 603.2.3 - SHOW THE REAR GRAB BAR TO
 COMPLY WITH 604.5.2 REAR WALL. THE REAR WALL GRAB BAR
 SHALL BE 36 INCHES (915 MM) LONG MINIMUM AND EXTEND
 FROM THE CENTERLINE OF THE WATER CLOSET 12 INCHES (305
 MM) MINIMUM ON ONE SIDE AND 24 INCHES (610 MM) MINIMUM
 ON THE OTHER SIDE.
  
  