Date |
Text |
2020-10-08 15:18:36 | 10/08/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED |
| CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 105.1. |
| |
| 2. PLEASE PROVIDE A DETAIL FOR WATER HEATER, HOW IT IS |
| GOING TO DRAIN OUTSIDE AND WITH THE METHOD IN WHICH |
| WILL BE USED TO PREVENT RODENT FROM ENTERING THROUGH |
| THAT DRAIN PER THE 2017 FBC R 2801.6.2 AND 2017 FBC R |
| 2606.1. |
| |
| 3. PLEASE PROVIDE THE SIGNITUE OF ALL INFORMATION, |
| DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT |
| SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO |
| THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 4. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| PLANS IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP |
| CODE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CATEGORY/FLORIDA?YEAR%5B%5D=C |
| URRENT+ADOPTION&PAGE=1 |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |