2020-10-14 12:18:05 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20100383 |
| |
| CODES IN EFFECT: |
| |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE DUCT SIZES ON THE MECHANICAL DRAWING. |
| FBC RES M1601.1 |
| |
| 2) PLEASE SHOW THE BATH EXHAUST FANS ON THE MECHANICAL |
| DRAWING AND SHOW THE DUCT TERMINATION. FBC RES TABLE |
| M1507.4 |
| |
| 3) PLEASE SHOW THE DRYER DUCT AND THE DUCT TERMINATION |
| LOCATION. FBC RES M1502 |
| |
| 4) IT APPEARS THE AHU?S LOCATION IS IN THE ATTIC. |
| PLEASE SHOW THE ATTIC ACCESS AND SIZE OF ACCESS ON THE |
| MECHANICAL DRAWING. FBC RES M1305.1.3 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |