Plan Review Notes
Plan Review Notes For Permit 20100383
Permit Number 20100383
Review Stop M
Sequence Number 1
Notes
Date Text
2020-10-14 12:18:051ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100383
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE DUCT SIZES ON THE MECHANICAL DRAWING.
 FBC RES M1601.1
  
 2) PLEASE SHOW THE BATH EXHAUST FANS ON THE MECHANICAL
 DRAWING AND SHOW THE DUCT TERMINATION. FBC RES TABLE
 M1507.4
  
 3) PLEASE SHOW THE DRYER DUCT AND THE DUCT TERMINATION
 LOCATION. FBC RES M1502
  
 4) IT APPEARS THE AHU?S LOCATION IS IN THE ATTIC.
 PLEASE SHOW THE ATTIC ACCESS AND SIZE OF ACCESS ON THE
 MECHANICAL DRAWING. FBC RES M1305.1.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  