2020-10-09 16:50:17 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20100372 |
| 10/9/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 2751 S |
| FLAGLER DR. INDICATES A 120,000 BTUH GAS RANGE ISSUED |
| UNDER PERMIT- 06061405. PLEASE PROVIDE A COMPLETE RISER |
| DRAWING THAT INCLUDES THE BRANCH LINE TO THE RANGE, THE |
| TOTAL LENGTH OF THE BRANCH, THE TOTAL DEVELOPED LENGTH |
| OF THE SYSTEM FROM THE METER TO THE MOST REMOTE OUTLET, |
| AND THE TOTAL BTUH LOAD OF THE SYSTEM - REFER TO |
| SECTIONS G2412.3, G2412.4, G2413.1, & G2413.2 FBC RES. |
| FUEL GAS. |
| |
| A) THE SUBMITTED WH SPECS INDICATE 3.5- 10.5 IN. W.C. |
| INPUT PRESSURE. SHOW THE DELIVERY PRESSURE AT THE |
| METER, THE LOCATION OF THE LOW PRESSURE REGULATOR, THE |
| REGULATOR OUTPUT PRESSURE, AND THE REQUIRED PIPE UNIONS |
| WITHIN 1 FT. OF EITHER SIDE OF THE REGULATOR- SECTIONS |
| G2421.1 & G2421.2. |
| |
| B) SUBMIT HIGHLIGHTED OR MARKED UP TO SHOW THE SELECTED |
| MODEL, THE MAX INLET AND OUTLET SIZE AND PRESSURES, AND |
| ORIFICE SIZE. THE SPECS CAN BE DEFERRED AND BE ONSITE |
| FOR INSPECTION. |
| |
| 2) PROVIDE A PLAN SHOWING THE INTERIOR OR EXTERIOR |
| LOCATION OF THE NEW WATER HEATER. IF INSTALLED ON THE |
| EXTERIOR SHOW THE REQUIRED CLEARANCES PER THE |
| MANUFACTURER'S SPECIFICATIONS, CLEARANCES FOR SERVICE |
| AND MAINTENANCE, AND VENTING CLEARANCES TO OPERABLE |
| OPENINGS INTO THE BUILDING- SECTION G2448.1 AND |
| G2427.1. |
| |
| 3) IF INSTALLED ON THE INTERIOR PROVIDE COMBUSTION AIR |
| AND VENTING PLANS- SECTIONS G2407.1 & G2427.1 |
| |
| 4) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1 |
| WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |