2020-10-14 18:38:29 | 10/14/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS |
| SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS |
| IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE |
| TDH CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2013 SECS. |
| 4.4.9, 4.4.9.1. |
| |
| 2. THE SUBMITTED TDH CALCULATIONS DO NOT APPEAR TO SHOW |
| THE FRICTION LOSS THROUGH ALL THE SYSTEM COMPONENTS. |
| THE CALCULATOR SHOWS THE PIPE, FITTINGS, VALVES, |
| HEATER, FILTER, ETC. BUT THERE IS NO FRICTION LOSS |
| ASSOCIATED WITH THESE ITEMS. PLEASE CLARIFY PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 3. THIS IS A MULTI-FAMILY DWELLINGS WATER USERS WILL BE |
| REQUIRED TO INSTALL A BACKFLOW PREVENTION ASSEMBLY AT |
| THE POINT OF DELIVERY. THE TYPE OF BACKFLOW ASSEMBLY |
| REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF HAZARD |
| POSED BY THE WATER USER. A REDUCED PRESSURE ZONE |
| BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER |
| THE CITY OF WEST PALM CROSS CONNECTION CONTROL MANUAL. |
| |
| 4. SUBMIT SPECIFICATIONS FOR THE CARTRIDGE FILTER AND |
| POOL PUMP PER THE WPB AMEND. TO FBC SEC. 107.2.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |