2020-10-19 15:06:21 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20100277 |
| 10/19/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 10672 GRANDE |
| BLVD SHOW A GAS PERMIT #01070853 FOR A 12 IN. W.C. |
| SYSTEM. THE NEW DRAWING SHOWS AN UPGRADE TO A 2 PSI. |
| SYSTEM. PLEASE SHOW THE LOCATION OF THE REQUIRED LOW |
| PRESSURE REGULATOR FOR THE EXISTING APPLIANCES, OR |
| PROVIDE A NEW REGULATOR- SECTIONS G2421.1 & G2421.2 FBC |
| RES. |
| |
| A) THE SPECS FOR THE GENERATOR SHOW 3.5- 7 IN. W.C. |
| INPUT GAS PRESSURE FOR THE GENERATOR. PLEASE CORRECT |
| THE 11 IN. W.C. NOTE AND SUBMIT MARKED UP OR |
| HIGHLIGHTED SPECS FOR THE NEW REGULATOR SHOWING MODEL |
| SELECTION, THE MAX INLET AND OUTLET SIZE AND PRESSURES, |
| SPRING DATA, AND ORIFICE SIZE. |
| |
| B) SHOW THE REQUIRED PIPE UNIONS WITHIN 1 FT. OF EITHER |
| SIDE OF THE REGULATOR -SECTION 2421.2(7) FBC RES. |
| |
| 2) SURVEY: SHOW THE CLEARANCE DISTANCE FROM THE |
| GENERATOR TO MECHANICAL AIR INTAKES AND OPERABLE |
| OPENINGS INTO THE BUILDING- SECTION R303.5.1 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |