2020-10-28 13:35:38 | NEW SFR |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected]. |
| CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| AMENDMENTS |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) PLEASE SHOW THE 1ST FLOOR TOILET ROOM DOOR TO COMPLY |
| WITH FBC R320.1.1 |
| ALL NEW SINGLE-FAMILY HOUSES, DUPLEXES, TRIPLEXES, |
| CONDOMINIUMS AND TOWNHOUSES SHALL PROVIDE AT LEAST ONE |
| BATHROOM, LOCATED WITH MAXIMUM POSSIBLE PRIVACY, WHERE |
| BATHROOMS ARE PROVIDED ON HABITABLE GRADE LEVELS, WITH |
| A DOOR THAT HAS A 29-INCH (737 MM) CLEAR OPENING. |
| HOWEVER, IF ONLY A TOILET ROOM IS PROVIDED AT GRADE |
| LEVEL, SUCH TOILET ROOMS SHALL HAVE A CLEAR OPENING OF |
| NOT LESS THAN 29 INCHES (737 MM).-- FBC A 404.2.3 CLEAR |
| WIDTH. CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS |
| SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE |
| STOP, WITH THE DOOR OPEN 90 DEGREES. |
| 2) PLEASE SHOW THE DOOR FROM THE GARAGE TO THE LIVING |
| SPACE TO COMPLY WITH FBC R302.5.1 OPENING PROTECTION. |
| OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL BE |
| EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 13/8 |
| INCHES (35 MM) IN THICKNESS, SOLID OR HONEYCOMB-CORE |
| STEEL DOORS NOT LESS THAN 13/8 INCHES (35 MM) THICK, OR |
| 20-MINUTE FIRE-RATED DOORS. |
| 3) PLEASE SHOW THE REQUIREMENT OF "TYPE X" DRYWALL FOR |
| THE GARAGE CEILING - FBC R302.6 |
| 4) PLEASE SHOW THE DRAFT STOPPING AT THE FLOOR FRAMING |
| TO COMPLY WITH FBC R302.12 DRAFTSTOPPING.IN COMBUSTIBLE |
| CONSTRUCTION WHERE THERE IS USABLE SPACE BOTH ABOVE AND |
| BELOW THE CONCEALED SPACE OF A FLOOR-CEILING ASSEMBLY, |
| DRAFTSTOPS SHALL BE INSTALLED SO THAT THE AREA OF THE |
| CONCEALED SPACE DOES NOT EXCEED 1,000 SQUARE FEET (92.9 |
| M2). DRAFTSTOPPING SHALL DIVIDE THE CONCEALED SPACE |
| INTO APPROXIMATELY EQUAL AREAS. |
| 5) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE |
| ENGINEER. (ELECTRONICALLY SIGNED TO BE USED IN |
| PROJECTDOX ELECTRONIC PLAN REVIEW) |