Plan Review Notes
Plan Review Notes For Permit 20100213
Permit Number 20100213
Review Stop P
Sequence Number 1
Notes
Date Text
2020-10-06 17:27:391ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20100213
 10/6/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED PLANS DO NOT SHOW ANY CHANGES THAT
 CORRELATE WITH REVISION 2 WHICH IS LISTED IN THE
 REVISION SCHEDULE ON EACH PLAN SHEET- SECTION 107.2.1
 WPB.
  
 2) SHEET P101: NEW FLOOR SINKS AND HAND SINKS IN THE
 KITCHEN SHALL CONNECT TO THE GREASE WASTE LINE- SECTION
 1003.3.1 FBC P AND SEC.90-126(7) CITY OF WPB CODE OF
 ORDINANCES. THE PLAN SHOWS CONNECTIONS INTO THE
 SANITARY- PLEASE CORRECT.
  
 3) P101, P102, P202, P203: PROVIDE A REVISED PLUMBING
 FIXTURE SCHEDULE CORRELATING WITH THE NEW P FIXTURES
 SHOWN ON THE PLANS- SECTION 107.2.1 WPB. PLEASE NOTE
 THE APPROVED PLAN UNDER PERMIT-17121049 HAD AN
 EQUIPMENT SCHEDULE ON SHEET P201. A COMPLETE REVIEW OF
 THE PLANS CANNOT BE COMPLETED WITHOUT THE SCHEDULE.
  
 4) P101: SUBMIT REVISED CIVIL PLANS SHOWING THE
 SANITARY AND GREASE WASTE LINE CONTINUATIONS AND
 LOCATION OF THE GREASE INTERCEPTOR- SECTION 107.2.1
 WPB.
  
 5) P101: PROVIDE GREASE WASTE CALCULATIONS AND AN
 EQUIPMENT SCHEDULE ON THE PLAN FOR THE GREASE
 INTERCEPTOR- SECTIONS 1003.3.4 & 1003.3.6 FBC P. PLEASE
 NOTE THAT ALL REVISIONS TO THE GREASE WASTE SYSTEM ON
 THE MASTER PERMIT SHALL ALSO BE APPLICABLE TO THE
 GREASE INTERCEPTOR PERMIT- 19060937.
  
 6) P102, P201: PROVIDE EQUIPMENT SCHEDULES FOR THE
 TANKLESS WATER HEATERS INDICATING THE MAKES, MODEL
 NUMBERS, BTUH CAPACITIES, LISTING STANDARDS, AND
 EFFICIENCY RATINGS- SECTION 624.1 FBC FG, AND TABLE
 C404.2 FBC EC. A) PROVIDE A FRONT ELEVATION VIEW OF THE
 WATER HEATER MOUNTING LOCATION SHOWING CLEARANCE
 DISTANCES FROM GRADE, OVERHEAD CONSTRUCTION, AND
 MECHANICAL AIR INTAKES AND OPERABLE OPENINGS INTO THE
 BUILDING- SECTION 624.1 AND 503.1 FBC FG.
  
 7) P102 & P202: SHOW THE LOCATION OF THE HOT WATER
 CIRCULATION PUMP AND PROVIDE AN EQUIPMENT SCHEDULE-
 SECTION 607.2.1 FBC P.
  
 8) P102, P201: INDICATE THE TYPE AND THICKNESS OF THE
 HOT WATER PIPING INSULATION TO BE INSTALLED ON THE
 EXTERIOR AND INTERIOR HOT WATER PIPING- TABLE C403.2.10
 FBC EC.
  
 9) P102 & P202: PROVIDE A PLUMBING DEVICE SCHEDULE
 INDICATING THE MAKES AND MODEL NUMBERS OF THE MIXING
 VALVES, BACKFLOW PREVENTERS, WATER HAMMER ARRESTORS,
 AND TRAP PRIMERS- SECTIONS 607.1.2, 608.1, 604.9,
 1002.4.1.1 FBC P. PLEASE INCLUDE THE LISTING NUMBERS OF
 THE DEVICES.
  
 10) P103: SHOW THE LOCATIONS OF TRAP PRIMERS ON THE
 RISER DRAWINGS- SECTION 1002.4.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  