Review Stop G
Sequence Number 1
Notes
Date Text
2020-10-21 14:37:041ST REVIEW FBC-2014 FUEL GAS
 REVISION PERMIT- 20100213
 MASTER PERMIT- 17121049
 10/20/2020
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2014
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2014
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2014
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2014
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2014
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2014
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2014
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2014
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P201 & P202: THE WOK (107.1) IS NOT SHOWN IN
 THE RISER. PLEASE ADD IT TO THE RISER AND CORRECT THE
 TOTAL 1,190 MBTU SHOWN AT THE METER. IT WOULD BE
 HELPFUL TO SHOW THE INDIVIDUAL LOADS FOR THE COOKING
 LINE APPLIANCES IN THE DRAWING- SECTIONS 402.2 FBC FG.
  
 2) SHOW THE DELIVERY PRESSURE AT THE METER, WHICH
 APPEARS TO BE 2 PSI, AND THE LOCATIONS OF STEP DOWN
 REGULATORS FOR REDUCING PRESSURES TO THE WATER HEATERS
 AND COOKING LINE APPLIANCES- SECTION 410.1 & 410.2.
 PLEASE INDICATE THE REQUIRED PIPE UNIONS WITHIN 1 FT.
 OF EITHER SIDE OF THE REGULATORS- SECTION 410.2(7).
 PLEASE IDENTIFY THE MAKES AND MODELS OF THE REGULATORS
 ON THE PLAN AND/OR SUBMIT MARKED UP OR HIGHLIGHTED
 SPECS FOR THE REGULATOR SHOWING THE SELECTED MODELS,
 THE MAX INLET AND OUTLET SIZE AND PRESSURES, SPRING
 DATA, AND ORIFICE SIZES- SECTION 410.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE COOKING
 APPLIANCES AND WATER HEATERS- SECTIONS 623.1 & 624.1.
  
 4) AN AUTOMATIC GAS SHUTOFF VALVE IS REQUIRED TO BE
 CONNECTED TO THE HOOD FIRE SUPPRESSION SYSTEM PER
 SEC.10.4.1 NFPA 96. PLEASE SHOW THE LOCATION OF THE
 VALVE ON THE RISER DRAWING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  