Plan Review Notes For Permit 20100209
Permit Number 20100209
Review Stop B
Sequence Number 3
Notes
Date Text
2020-12-21 13:31:3112/18/2020 TALKED TO SOFIA SCIALLA (CONTRACTOR). SHE
 SAID OK TO PASS BUILDING REVIEW WITH PROVISO. JG.
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1-THERE ARE 2 SEPARATE PERMIT APPLICATIONS:
 MAIN HOUSE 20100209 AND GUEST CASITA 20120600. ALL
 SUBPERMITS TO REFERENCE BOTH PERMIT NUMBERS.
  
 2- ENERGY CALCULATIONS:
 A)PROVIDE SEPARATE ENERGY CALCULATIONS FOR THE GUEST
 CASITA. SEC. R101.3 FBC-ENERGY CONSERVATION.
 B)ENERGY CALCULATIONS SUBMITTED. NEED INFORMATION ON
 TOP OF FORM: OWNER, BUILDER, PERMIT OFFICE AND
 JURISDICTION NUMBER 604700.
 C)REVISE A/C AREA. MAIN HOUSE AND GUEST CASITA AREA TO
 BE DONE ON SEPARATE FORMS FOR EACH BUILDING.
 D)REVISE WALL TYPE IN ITEM #9 ON PAGE 1 OF 6. ACCORDING
 TO PLANS THESE ARE WOOD BEARING WALLS.
 E)PAGE 2 OF 6 SHOWS A KITCHEN IN-THE GUEST CASITA.
 THERE IS NOT KITCHEN IN THE GUEST CASITA.
 F)REVISE/CLARIFY DOORS INFORMATION ON PAGE 4 OF 6.
 WHERE IS THE 6 X 8 WOOD DOOR BY THE KITCHEN ZONE. ALSO,
 WHERE ARE THE OTHER TWO WOOD DOORS?. NOTE: GLAZING IN
 DOORS NEEDS TO BE INCLUDED IN THE WINDOW GLAZING AREA.
 G)PROVIDE THE NAME OF PERSON GENERATING THE REPORT AS
 REQUIRED BY SEC. R405.4.2.1 FBC- ENERGY CONSERVATION.
 H)REVISE WINDOWS OVERHANG SEPARATION TO MATCH PLANS.
  
 3-AS DISCUSSED W/ SOFIA SCIALLA, RESUBMIT PRODUCT
 APPROVALS (EXCEPT FOR ROOFING PRODUCT APPROVALS).
 COORDINATE WITH ENGINEER'S LETTER, AND PRODUCT
 APPROVALS LISTED ON THE PRODUCT APPROVAL SCHEDULE ON
 SHEET 3 OF 10.
  
 4-PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE
 INSULATION REVIEWED/APPROVED BY THE DESIGNER OF RECORD.
  
 5-HANDRAILS AND GUARDRAILS DEFERRED SUBMITTAL: PROVIDE
 SHOP DRAWINGS REVIEWED BY THE DESIGN PROFESSIONAL OF
 RECORD.