2021-01-06 17:47:16 | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20100209 |
| 1/6/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. A COMPLETE REVIEW OF THE |
| GAS PLANS WAS NOT COMPLETED AT THIS TIME DUE A LACK OF |
| INFORMATION PROVIDED ON THE PLANS. PLEASE REVIEW THE |
| COMMENTS BELOW AND RESUBMIT COMPLIANT PLANS AND |
| SPECIFICATIONS. |
| |
| 1) SHEET 10 GAS RISER CORRECTIONS- FBC-17 RES. FUEL |
| GAS: |
| A) PROVIDE THE DELIVERY PRESSURE AT THE METER- G2413.1. |
| B) CORRECT THE TOTAL BTU LOAD TO 1020 K- SECTION |
| G2413.2. |
| C) PROVIDE THE TYPES AND SIZES OF BRANCH PIPING TO THE |
| TANKLESS WATER HEATERS AND THE RANGE- G2413.4.1 & |
| G2413.4.2. |
| D) LIST THE PIPE SIZING TABLES USED TO DESIGN THE |
| SYSTEM- G2413.3 & G2413.4. |
| |
| 2) LIST THE MAKES AND MODELS OF THE WATER HEATERS AND |
| SUBMIT MANUFACTURER'S SPECIFICATIONS- G2448.1. THE |
| SPECS AND INSTALL MANUALS MAY BE DEFERRED AND SUBMITTED |
| AT A LATER DATE, BUT ALL SPECS AND INSTALL MANUALS |
| SHALL BE ONSITE AT TIME OF INSPECTION- SECTIONS 107.2.1 |
| AND 107.3.4.1 WPB. |
| |
| 3) LIST THE MAKES AND MODELS OF THE FIREPLACE, FIREPIT, |
| POOL HEATER, DRYER, RANGE, AND BBQ GRILL ON THE PLAN |
| AND SUBMIT MANUFACTURER'S SPECIFICATIONS. PLEASE NOTE |
| THE SPECS AND INSTALL MANUALS MAY BE DEFERRED AND |
| SUBMITTED AT A LATER DATE, BUT ALL SPECS AND INSTALL |
| MANUALS SHALL BE ONSITE AT TIME OF INSPECTION- SECTIONS |
| 107.2.1 AND 107.3.4.1 WPB. |
| |
| 4) SUBMIT MARKED UP OR HIGHLIGHTED REGULATOR SPECS |
| SHOWING THE SELECTED MODELS, THE MAX INLET AND OUTLET |
| SIZES AND PRESSURES AND ORIFICE SIZES. THE SPECS MAY BE |
| DEFERRED AND BE ONSITE FOR INSPECTION. |
| |
| 5) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE GAS |
| RANGE AND THE FIREPLACE AND SHOW HOW THE AIR IS BEING |
| PROVIDED- SECTION G2407.1. |
| |
| 6) PROVIDE MAKEUP AIR CALCULATIONS FOR THE DRYER AND |
| SHOW HOW THE AIR IS BEING PROVIDED- G2439.5. |
| |
| 7) PROVIDE A VENTING DIAGRAM FOR THE FIREPLACE SHOWING |
| THE TYPE AND SIZE OF VENT FLUE, VENT RUN, AND |
| TERMINATION LOCATION- G2427.8(3). |
| |
| 8) PLEASE SHOW THE LOCATION OF THE FIREPIT ON THE FLOOR |
| PLAN DRAWINGS- SECTION 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |