Plan Review Notes
Plan Review Notes For Permit 20100186
Permit Number 20100186
Review Stop P
Sequence Number 1
Notes
Date Text
2020-10-06 13:30:5110/06/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB PLUMBING PERMIT FOR AUTOFILL PRESSURE VAUCCUM
 BREAKER HAS TO BE A STAND-ALONE TYPE, THIS AUTO-FILL
 ALSO REQUIRES TO HAVE A REDUCED PRESSURE ZONE VACUUM
 BREAKER AT THE METER WHICH IT UNIT HAS TO BE CERTIFIED
 BY THE CITY OF WEST PALM BEACH UNDER THE CROSS
 CONNECTION PROGRAM AS THIS IS A CONTAINMENT BACKFLOW
 DEVICE. THE PVB IS AN ISOLATION DEVICE THAT CAN BE
 CERTIFIED BY THE PLUMBING CONTRACTOR BEFORE A FINAL
 INSPECTION. PLEASE SUBMIT A SEPARATE APPLICATION WITH
 THE MANUFACTURER?S SPECIFICATIONS FOR THE BACKFLOW
 PREVENTERS. THE MAKE, MODEL, AND SIZE OF THE DEVICE
 SHALL BE LISTED IN THE DESCRIPTION OF THE WORK SECTION
 ON THE PERMIT APPLICATION. THESE DEVICES REQUIRE A
 DOCUMENT THAT NEEDS TO SHOW THE DEVICE IS LEAD-FREE
 WHICH CONTAINS NOT MORE THAN 0.25-PERCENT LEAD AND
 APPROVED DEVICES LISTED AND PUBLISHED BY THE UNIVERSITY
 OF SOUTHERN CALIFORNIA (USC).
  
 2. PLEASE PROVIDE MANUFACTURES SPECIFICATIONS FOR THE P
 CC 200 CARTRIDGE FILTER PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1, INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. A SOLAR COVER REQUIRED PER 2017 FBC RE 403.10.3.
  
 4. PLEASE PROVIDE DOCUMENTATION THAT THE GAS AND SPA
 HEATERS SHALL HAVE A MINIMUM THERMAL EFFICIENCY OF 82 %
 FOR HEATERS MANUFACTURED ON OR AFTER APRIL 16, 2013,
 WHEN TESTED IN ACCORDANCE WITH ANSI Z 21.56.
  
 5. IDENTIFY AND SHOW ON THE PUMP CURVE WHICH CURVE KEY
 IS SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL.
 THIS IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM
 THE TDH CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2013
 SECS. 4.4.9, 4.4.9.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved