Plan Review Notes
Plan Review Notes For Permit 20100167
Permit Number 20100167
Review Stop G
Sequence Number 1
Notes
Date Text
2020-10-20 10:31:391ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20100167
 10/20/29
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER DRAWING: PROVIDE AN LP GAS RISER DRAWING
 SHOWING THE TYPES AND SIZES OF PIPING; TOTAL DEVELOPED
 LENGTH OF THE SYSTEM AND LENGTHS OF BRANCHES TO ALL NEW
 AND EXISTING LP APPLIANCES OR EQUIPMENT; TOTAL BTUH
 LOAD OF THE SYSTEM AND INDIVIDUAL LOADS OF APPLIANCES
 OR EQUIPMENT- SECTIONS G2412.3, G2412.4, G2413.2,
 G2413.4.1, G2413.4.2, G2412.3, G2412.4 FBC RES.
  
 A) SHOW THE LOCATIONS OF SHUTOFF VALVES, LOCATIONS AND
 MAKES AND MODELS OF REGULATORS INCLUDING INLET AND
 OUTLET PRESSURES, LOCATIONS OF UNIONS, RISERS AND FLEX
 CONNECTORS; AND A LIST OF GAS PIPE SIZING TABLES-
 SECTIONS G2420, G2421, & G2413.4(1)- G2413.4(21) FBC
 RES. PLEASE NOTE THE SUBMITTED PIPE SIZING TABLE IN THE
 GAS SUBMITTAL PACKAGE IS FOR NATURAL GAS. PLEASE SUBMIT
 LP PIPE SIZING TABLES.
  
 2) PLEASE MARK UP THE SUBMITTED SURVEY TO SHOW THE
 LOCATION OF THE NEW LP TANK AND REQUIRED 10 FT.
 CLEARANCES DISTANCES FROM THE TANK TO THE BUILDING, AND
 ADJACENT PROPERTY LINES- TABLE 6.3.1.1 NFPA 58. PLEASE
 SHOW THE PIPING RUN ON THE SURVEY FROM THE TANK TO THE
 GENERATOR- SECTION 107.2.1 WPB.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 500-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE
 BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED)
 IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE
 REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN
 SECTION 5.2.1.1 NFPA 58.
  
 4) PROVIDE LP TANK INSTALLATION AS REQUIRED BY NFPA 58:
  
 A) ENGINEERING FOR ANCHORING THE TANK TO PREVENT
 FLOTATION, COLLAPSE, OR LATERAL MOVEMENT- SECTION
 6.6.1.6. PLEASE INCLUDE A FRONT AND SIDE ELEVATION VIEW
 THAT SHOWS THE BURIAL DEPTH, ANCHORING BASE MATERIAL,
 AND THE TYPES, SIZES, AND NUMBERS OF ANCHORS, CABLES OR
 STRAPS, AND THE TYPE OF PROTECTIVE SLEEVES FOR THE
 CABLES OR STRAPS.
  
 B) SHOW HOW THE TANK WILL BE PROTECTED AGAINST
 CORROSION BY INSTALLATION OF A CATHODIC PROTECTION
 SYSTEM CONSISTING OF A SACRIFICIAL ANODE OR AN
 IMPRESSED CURRENT ANODE PER SECTIONS 5.2.1.11 &
 6.6.6.1(I) NFPA 58. INDICATE THE TYPE OF PROTECTION AND
 HOW IT WILL BE TESTED- SECTION 6.17.1.
  
 5) THE SURVEY HAS BEEN INCORRECTLY MARKED UP TO SHOW A
 5 FT. CLEARANCE FOR THE GENERATOR TO WINDOWS AND DOORS,
 HOWEVER A 10 FT. CLEARANCE TO MECHANICAL AND GRAVITY
 AIR INTAKES IS REQUIRED PER SECTION R303.5.1 FBC RES-
 PLEASE CORRECT THE DRAWING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  