Plan Review Notes
Plan Review Notes For Permit 20100119
Permit Number 20100119
Review Stop B
Sequence Number 2
Notes
Date Text
2021-03-08 09:55:04WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20100119
 ADD: 1900 CONSULATE PL. SUITE: 2102
 CONT: MOSS DEVCO INC
 TEL: 561-644-0302
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. MARCH 08TH/ 2021
 ACTION: DENIED
  
 NOTICE ONLY!!!! 4X FEE / NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B). WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT FINDS
 IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW.
  
  
 0.1) NEW COMMENT. THE SUBMITTED PLANS DID NOT KEEP THE
 SAME NAMING CONVENTION TO BE ABLE TO SEE VERSION 1 AND
 VERSION 2 AT THE SAME TIME, TO SEE WHAT IS NEW, CHANGED
 AND OR DELETED.
 107.2.1.3. QUALITY OF PLANS. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENT POLICY OTHER STANDARDS FOR
 THE PLANS AND SPECIFICATIONS IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORD
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 0.2) NEW COMMENT. NEW SHEETS BARRY K COVERSHEET REV.
 AND BARRY KNIGHT EXTG FLOOR BOTH SUBMITTED 2/25/2021 DO
 NOT HAVE ANY SIGNATURE AND SEAL PRINTED NOR DIGITAL.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 DOCUMENT IN THE FILE FOLDER, SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED ON DIGITALLY SIGNED AND
 SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.
  
 1) 2ND ROUND OF COMMENTS. THE REVISED COVERSHEET STILL
 HAS THE SAME COMMENT ABOUT THE REQUIRED CODE
 REQUIREMENTS. THERE IS AN ADDITIONAL STATEMENT SEE
 ATTACHED UNDERLAYMENT SPECIFICATIONS. THERE ARE NO
 ATTACHED UNDERLAYMENT SPECIFICATIONS ATTACHED. AGAIN,
 WE DO NOT WANT TO SEE SPECIFICATIONS. WE REQUIRE THE
 ACTUAL TEST RESULTS AS STATED IN THE FIRST REVIEW.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 W.P.B. ADMINISTRATIVE CODE/2017 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "CODE SECTIONS SHALL NOT BE CITED
 AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
  
  
 1ST ROUND COMMENTS. COVERSHEET C-1. THERE IS A
 STATEMENT ABOUT SOUND FLOOR UNDERLAYMENT TO MEET THE
 FBC 2017, 6TH EDITION. PLEASE CONFIRM IF THERE IS FLOOR
 FINISHES TO BE REMOVED AND NEW FLOOR UNDERLAYMENT AND
 THE TYPE OF NEW FLOOR FINISHES. IF THERE ARE NO NEW
 FLOOR FINISHES PLEASE REMOVE THIS NOTE.
  
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS SHOWING
 COMPLIANCE WITH:
 TYPE I AND II BUILDINGS
 1A)2ND REQUEST. FBC-B 2017 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) 2ND REQUEST. FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) 2ND REQUEST. FLAME SPREAD- FBC-B 2017 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2) COMPLIED. COVERSHEET C-1 CLASSIFIES THE BUILDING AS
 A 21 STORY FULLY SPRINKLERED HIGH RISE. CONSTRUCTION
 TYPE IIB. PLEASE REVIEW THE 2017 FBC-B TABLE 504.4.
 TYPE IIB CONSTRUCTION CAN ONLY GO 5 STORIES TALL. FOR A
 21 STORY R-2 HIGH RISE THE CONSTRUCTION TYPE WOULD BE
 REQUIRED TO BE TYPE: I-A.
  
 3) SHEET 01 THE EXISTING FLOOR PLAN:
 3A) COMPLIED. THE BUILDING DATA LIST THIS BUILDING
 CONSTRUCTION TYPE AS VB. PLEASE CORRECT THE PLANS. FOR
 A 21 STORY
 R-2 HIGH RISE THE CONSTRUCTION TYPE WOULD BE REQUIRED
 TO BE TYPE: I-A. 2017 FBC-B TABLE 504.4.
  
 3B) COMPLIED.T HE BUILDING DATA LIST THE OCCUPANCY AS
 R-3. PLEASE NOTE R-3 CONSTRUCTION IS FOR 1 & 2 FAMILY
 DWELLINGS, THIS IS A 21 STORY HIGHRISE RESIDENTIAL R-2
 OCCUPANCY. 2017 FBC-B 310.4, PLEASE UPDATE PLANS.
  
 4) SHEET 02 THE PROPOSED FLOOR PLAN:
 4A) COMPLIED. IN THE BUILDING DATA BOX THE BUILDING
 DATA IS LEFT BLANK. FOR A 21 STORY R-2 HIGH RISE THE
 CONSTRUCTION TYPE WOULD BE REQUIRED TO BE TYPE: I-A.
 2017 FBC-B TABLE 504.4.
  
 4B 2ND REUEST. SEMI-COMPLIED, NO HEIGTH GIVEN. SHEET 02
 THE PROPOSED WORK, NOTE # 3 INDICATES THAT THE EXISTING
 SHOWER IS GOING TO BE ENLARGED, PLANS ARE SILENT AS TO
 THE TYPE OF BACKER BOARD TO BE INSTALLED NOR THE HEIGHT
 OF THE TILE IN THE SHOWER.
  
 4B)(1) COMPLIED. 2017 FBC-B 2509.2 BASE FOR TILE.
 MATERIALS USED AS A BASE FOR WALL TILE IN TUB AND
 SHOWER AREAS AND WALLS AND CEILING PANELS IN SHOWER
 AREAS SHALL BE OF MATERIALS LISTED IN TABLE 2509.2 AND
 INSTALLED IN ACCORDANCE WITH MANUFACTURERS
 RECOMMENDATIONS. WATER RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C840 AND THE MANUFACTURES
 RECOMMENDATIONS.
  
 4B)( 2) 2ND REQUEST, NO HEIGTH GIVEN FOR SHOWER. 2017
 FBC-B SHOWERS & TUBS 1210.3. SHOWER COMPARTMENTS AND
 BATHTUBS WITH INSTALLED SHOWER HEADS SHALL BE FINISHED
 WITH A NONABSORBENT SURFACE TO A HEIGHT NOT LESS THAN
 72 INCHES ABOVE THE DRAIN INLET.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  