2021-01-11 11:49:25 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20100119 |
| ADD: 1900 CONSULATE PL. SUITE: 2102 |
| CONT: MOSS DEVCO INC |
| TEL: 561-644-0302 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: JAN. 11TH/ 2021 |
| ACTION: DENIED |
| |
| 1) COVERSHEET C-1. THERE IS A STATEMENT ABOUT SOUND |
| FLOOR UNDERLAYMENT TO MEET THE FBC 2017, 6TH EDITION. |
| PLEASE CONFIRM IF THERE IS FLOOR FINISHES TO BE REMOVED |
| AND NEW FLOOR UNDERLAYMENT AND THE TYPE OF NEW FLOOR |
| FINISHES. IF THERE ARE NO NEW FLOOR FINISHES PLEASE |
| REMOVE THIS NOTE. |
| |
| FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE ALL THREE TEST REPORTS SHOWING |
| COMPLIANCE WITH: |
| TYPE I AND II BUILDINGS |
| 1A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| |
| 1B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. |
| |
| 1C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 2) COVERSHEET C-1 CLASSIFIES THE BUILDING AS A 21 STORY |
| FULLY SPRINKLERED HIGH RISE. CONSTRUCTION TYPE IIB. |
| PLEASE REVIEW THE 2017 FBC-B TABLE 504.4. TYPE IIB |
| CONSTRUCTION CAN ONLY GO 5 STORIES TALL. FOR A 21 STORY |
| R-2 HIGH RISE THE CONSTRUCTION TYPE WOULD BE REQUIRED |
| TO BE TYPE: I-A. |
| |
| 3) SHEET 01 THE EXISTING FLOOR PLAN: |
| 3A) THE BUILDING DATA LIST THIS BUILDING CONSTRUCTION |
| TYPE AS VB. PLEASE CORRECT THE PLANS. FOR A 21 STORY |
| R-2 HIGH RISE THE CONSTRUCTION TYPE WOULD BE REQUIRED |
| TO BE TYPE: I-A. 2017 FBC-B TABLE 504.4. |
| |
| 3B) THE BUILDING DATA LIST THE OCCUPANCY AS R-3. PLEASE |
| NOTE R-3 CONSTRUCTION IS FOR 1 & 2 FAMILY DWELLINGS, |
| THIS IS A 21 STORY HIGHRISE RESIDENTIAL R-2 OCCUPANCY. |
| 2017 FBC-B 310.4, PLEASE UPDATE PLANS. |
| |
| 4) SHEET 02 THE PROPOSED FLOOR PLAN: |
| 4A) IN THE BUILDING DATA BOX THE BUILDING DATA IS LEFT |
| BLANK. FOR A 21 STORY R-2 HIGH RISE THE CONSTRUCTION |
| TYPE WOULD BE REQUIRED TO BE TYPE: I-A. 2017 FBC-B |
| TABLE 504.4. |
| |
| 4B) SHEET 02 THE PROPOSED WORK, NOTE # 3 INDICATES THAT |
| THE EXISTING SHOWER IS GOING TO BE ENLARGED, PLANS ARE |
| SILENT AS TO THE TYPE OF BACKER BOARD TO BE INSTALLED |
| NOR THE HEIGHT OF THE TILE IN THE SHOWER. |
| |
| 4B)(1) 2017 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED |
| AS A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND |
| WALLS AND CEILING PANELS IN SHOWER AREAS SHALL BE OF |
| MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN |
| ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER |
| RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE |
| FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN |
| INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND |
| THE MANUFACTURE?S RECOMMENDATIONS. |
| |
| 4B)( 2) 2017 FBC-B SHOWERS & TUBS 1210.3. SHOWER |
| COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS |
| SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A |
| HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET. |
| |
| 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| RETIRED. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |