Plan Review Notes
Plan Review Notes For Permit 20100119
Permit Number 20100119
Review Stop B
Sequence Number 1
Notes
Date Text
2021-01-11 11:49:25WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20100119
 ADD: 1900 CONSULATE PL. SUITE: 2102
 CONT: MOSS DEVCO INC
 TEL: 561-644-0302
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JAN. 11TH/ 2021
 ACTION: DENIED
  
 1) COVERSHEET C-1. THERE IS A STATEMENT ABOUT SOUND
 FLOOR UNDERLAYMENT TO MEET THE FBC 2017, 6TH EDITION.
 PLEASE CONFIRM IF THERE IS FLOOR FINISHES TO BE REMOVED
 AND NEW FLOOR UNDERLAYMENT AND THE TYPE OF NEW FLOOR
 FINISHES. IF THERE ARE NO NEW FLOOR FINISHES PLEASE
 REMOVE THIS NOTE.
  
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS SHOWING
 COMPLIANCE WITH:
 TYPE I AND II BUILDINGS
 1A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2) COVERSHEET C-1 CLASSIFIES THE BUILDING AS A 21 STORY
 FULLY SPRINKLERED HIGH RISE. CONSTRUCTION TYPE IIB.
 PLEASE REVIEW THE 2017 FBC-B TABLE 504.4. TYPE IIB
 CONSTRUCTION CAN ONLY GO 5 STORIES TALL. FOR A 21 STORY
 R-2 HIGH RISE THE CONSTRUCTION TYPE WOULD BE REQUIRED
 TO BE TYPE: I-A.
  
 3) SHEET 01 THE EXISTING FLOOR PLAN:
 3A) THE BUILDING DATA LIST THIS BUILDING CONSTRUCTION
 TYPE AS VB. PLEASE CORRECT THE PLANS. FOR A 21 STORY
 R-2 HIGH RISE THE CONSTRUCTION TYPE WOULD BE REQUIRED
 TO BE TYPE: I-A. 2017 FBC-B TABLE 504.4.
  
 3B) THE BUILDING DATA LIST THE OCCUPANCY AS R-3. PLEASE
 NOTE R-3 CONSTRUCTION IS FOR 1 & 2 FAMILY DWELLINGS,
 THIS IS A 21 STORY HIGHRISE RESIDENTIAL R-2 OCCUPANCY.
 2017 FBC-B 310.4, PLEASE UPDATE PLANS.
  
 4) SHEET 02 THE PROPOSED FLOOR PLAN:
 4A) IN THE BUILDING DATA BOX THE BUILDING DATA IS LEFT
 BLANK. FOR A 21 STORY R-2 HIGH RISE THE CONSTRUCTION
 TYPE WOULD BE REQUIRED TO BE TYPE: I-A. 2017 FBC-B
 TABLE 504.4.
  
 4B) SHEET 02 THE PROPOSED WORK, NOTE # 3 INDICATES THAT
 THE EXISTING SHOWER IS GOING TO BE ENLARGED, PLANS ARE
 SILENT AS TO THE TYPE OF BACKER BOARD TO BE INSTALLED
 NOR THE HEIGHT OF THE TILE IN THE SHOWER.
  
 4B)(1) 2017 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED
 AS A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND
 WALLS AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 4B)( 2) 2017 FBC-B SHOWERS & TUBS 1210.3. SHOWER
 COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS
 SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A
 HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  