Plan Review Notes
Plan Review Notes For Permit 20100104
Permit Number 20100104
Review Stop E
Sequence Number 5
Notes
Date Text
2021-02-11 12:57:07ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-1 LOAD CALCULATION FOR FEEDER TO PANEL EV NOT IN
 ACCORDANCE WITH 625.40.
  
 PAGE E-2 LOAD CALCULATION FOR FEEDER TO EAST LOT PANEL
 NOT IN ACCORDANCE WITH 625.40.
  
 PAGE AREA 1 SHOWS A FEEDER WITH 3 #1 AND A #6 AND
 ANOTHER BRANCH GOING TO THE HANDICAP SPACE WHAT FEEDS
 THE HANDICAP SPACE. WHERE IS THE HANDICAP FED FROM?
 125A MAIN/ 200A MAIN?
  
 PAGE AREA 2 SHOWS 3/0 GOING TO THE PANEL, LOAD
 CALCULATION SHOWN FOR THESE CONDUCTORS IS NOT PER
 625.40. 200A MAIN/300A MAIN?
  
 PLEASE PROVIDE A VOLTAGE DROP CALCULATION BASED ON
 625.40 LOAD CALCULATION.
  
 DO YOU HAVE LOAD MANAGEMENT IF SO PLEASE EXPLAN HOW IT
 WORKS.
  
  