Plan Review Notes For Permit 20100104 |
Permit Number |
20100104 |
|
Review Stop |
E |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2021-02-11 12:57:07 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | PAGE E-1 LOAD CALCULATION FOR FEEDER TO PANEL EV NOT IN | | ACCORDANCE WITH 625.40. | | | | PAGE E-2 LOAD CALCULATION FOR FEEDER TO EAST LOT PANEL | | NOT IN ACCORDANCE WITH 625.40. | | | | PAGE AREA 1 SHOWS A FEEDER WITH 3 #1 AND A #6 AND | | ANOTHER BRANCH GOING TO THE HANDICAP SPACE WHAT FEEDS | | THE HANDICAP SPACE. WHERE IS THE HANDICAP FED FROM? | | 125A MAIN/ 200A MAIN? | | | | PAGE AREA 2 SHOWS 3/0 GOING TO THE PANEL, LOAD | | CALCULATION SHOWN FOR THESE CONDUCTORS IS NOT PER | | 625.40. 200A MAIN/300A MAIN? | | | | PLEASE PROVIDE A VOLTAGE DROP CALCULATION BASED ON | | 625.40 LOAD CALCULATION. | | | | DO YOU HAVE LOAD MANAGEMENT IF SO PLEASE EXPLAN HOW IT | | WORKS. | | | | |
|