2021-01-08 17:05:44 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| FLORIDA BUILDING CODE 2017 6TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| NFPA 70 2014 EDITION |
| |
| JAKE LEAHY BN, BU, PX |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| 1) VALUE OF JOB DOES NOT INCLUDE THE VALUE OF THE |
| CHARGERS. |
| |
| FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| 2) ALL PAGES ARE NOT SIGNED IF THEY ARE FROM AN |
| ENGINEERING FIRM THEY WILL NEED TO SIGNED AND SEALED BY |
| THAT FIRM. SITE PLAN NOT SIGNED, |
| |
| PLAN IS NOT DIGITALLY SIGNED BY THE DESIGNER OF RECORD |
| |
| PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN |
| PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS |
| 471.003(2)(H); 471.025; FBC 107.2.1 |
| |
| 3) PLEASE SHOW A BETTER DETAIL OF EXACTLY WHERE |
| PANELS(SERVICE) AND CHARGERS ARE TO BE INSTALLED IN |
| PARKING LOT. SITE PLAN IS TO VAGUE. PLAN NEEDS TO SHOW |
| IF BOLLARDS OR SOME OTHER TYPE OF PROTECTION WILL BE |
| REQUIRED FOR PROTECTION OF THE SERVICE, PANELS, OR |
| CHARGERS AS INSTALLED. |
| |
| 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| RECORDS MANAGEMENT. |