Plan Review Notes
Plan Review Notes For Permit 20100104
Permit Number 20100104
Review Stop B
Sequence Number 2
Notes
Date Text
2021-02-11 07:53:13PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE RE-SUBMITTED PLANS DO NOT COMPLETELY ADDRESS THE
 ACCESSIBILITY ISSUE. THE SITE PLAN INDICATES THAT THE
 EVC STATIONS ARE LOCATED IN TWO DIFFERENT PARKING AREAS
 WHICH ARE FOR TWO DIFFERENT BUILDINGS. THE AREAS ARE
 NAMED AREA 1 AND AREA 2.
 AREA 1 HAS SIX EXISTING ACCESSIBLE PARKING SPACES AND
 THIS PARKING LOT SERVES THE DIALYSIS CENTER. THERE WILL
 BE A TOTAL OF 5 EV SPACES IN THIS AREA. THE PLAN
 INDICATES THAT AN EVC STATION WILL BE INSTALLED AT ONE
 OF THE EXISTING ACCESSIBLE SPACES. THIS IS ACCEPTABLE.
 AREA 2 HAS EIGHT EXISTING ACCESSIBLE PARKING SPACES AND
 THIS LOT SERVES THE AMBULATORY SURGICAL CENTER. THERE
 WILL BE A TOTAL OF 8 EV SPACES IN THIS AREA. THERE ARE
 NO ACCESSIBLE EVC STATIONS INDICATED ON THE PLANS FOR
 AREA 2. AT LEAST ONE OF THESE CHARGING STATIONS SHOULD
 BE ACCESSIBLE. FBC ACCESSIBILITY CHAPTERS 3, 4 AND 5
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved