2020-11-06 15:21:01 | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20100062 |
| 11/6/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHOW THE TOTAL LOAD OF THE SYSTEM AND SHOW THE |
| COOKTOP LOAD- SECTIONS G2412.3, G2412.4, & G2413.2 FBC |
| RES. |
| |
| 2) PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF THE |
| PIPING FROM THE METER TO THE MOST REMOTE OUTLET- |
| SECTIONS G2413.4.1 AND G2413.4.2 FBC RES. |
| |
| 3) PROVIDE THE PIPE SIZING TABLES FOR THE SYSTEM ON THE |
| RISER- TABLES- G2413.4(1) ? G2413.4(8) FBC RES. |
| |
| 4) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1 |
| WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| |
| 5) PLEASE CORRECT THE NOTE ON THE SURVEY TO INDICATE |
| THE MINIMIUM10 FT. CLEARANCE TO MECHANICAL AND GRAVITY |
| AIR INTAKES INTO THE BUILDING- SECTION R303.5.1 RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |