Plan Review Notes
Plan Review Notes For Permit 20100046
Permit Number 20100046
Review Stop P
Sequence Number 2
Notes
Date Text
2021-04-27 10:04:3420100046 529 S FLAGLER DR # 6E
  
 PLUMBING COMMENTS: APPROVED WITH PROVISO
 PROVISO: NO VERTICAL RISE IN FIXTURE DRAIN BETWEEN TRAP
 AND VENT; SEE FBC PL 909.2
 THE TOTAL FALL IN A FIXTURE DRAIN DUE TO PIPE SLOPE
 SHALL NOT EXCEED THE DIAMETER OF THE FIXTURE DRAIN, NOR
 SHALL THE VENT CONNECTION TO A FIXTURE DRAIN, EXCEPT
 FOR WATER CLOSETS, BE BELOW THE WEIR OF THE TRAP.
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  