2020-12-01 14:31:02 | 3RD REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20100012 |
| 12/1/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| FAILED COMMENTS FROM THE 1ST AND 2ND REVIEW ARE LISTED |
| BELOW WITH ADDITIONAL NOTES. |
| |
| 3) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| 500-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE |
| BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED) |
| IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE |
| REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN |
| SECTION 5.2.1.1 NFPA 58. TANK SPECS NOT SUBMITTED. |
| PLEASE PROVIDE THE TANK SPEC SHEET. |
| |
| 4A) FAILED. PROVIDE LP TANK INSTALLATION DETAILS AS |
| REQUIRED BY NFPA 58- ENGINEERING FOR ANCHORING THE TANK |
| TO PREVENT FLOTATION, COLLAPSE, OR LATERAL MOVEMENT- |
| SECTION 6.6.1.6. PLEASE INCLUDE A FRONT AND SIDE |
| ELEVATION VIEW THAT SHOWS THE BURIAL DEPTH, ANCHORING |
| BASE MATERIAL, AND THE TYPES, SIZES, AND NUMBERS OF |
| ANCHORS, CABLES OR STRAPS, AND THE TYPE OF PROTECTIVE |
| SLEEVES FOR THE CABLES OR STRAPS. PLEASE PROVIDE |
| ENGINEERING FOR INSTALLATION OF THE LP TANK. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |