Plan Review Notes
Plan Review Notes For Permit 20100012
Permit Number 20100012
Review Stop G
Sequence Number 2
Notes
Date Text
2020-11-18 12:37:452ND REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20100012
 11/18/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW
 WITH ADDITIONAL NOTES.
  
 1) FAILED. SURVEY: INDICATE THE REQUIRED 10 FT.
 CLEARANCE DISTANCE FOR THE UG TANK TO THE DRIVEWAY-
 SECTION 6.6.6.1(B) & (C) NFPA 58-14. TANKS INSTALLED
 WITH 10 FT. SHALL BE INSTALLED 18 IN. BELOW GRADE OR
 VEHICLE PROTECTION SHALL BE PROVIDED. THE CLEARANCE
 DISTANCE FROM THE UG TANK TO THE DRIVEWAY NOT SHOWN.
 INSTALLATION DETAILS FOR DOME AND COVER NOT PROVIDED.
  
 3) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 500-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE
 BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED)
 IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE
 REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN
 SECTION 5.2.1.1 NFPA 58. TANK SPECS NOT SUBMITTED.
  
 4) FAILED. PROVIDE LP TANK INSTALLATION DETAILS AS
 REQUIRED BY NFPA 58:
  
 A) FAILED. ENGINEERING FOR ANCHORING THE TANK TO
 PREVENT FLOTATION, COLLAPSE, OR LATERAL MOVEMENT-
 SECTION 6.6.1.6. PLEASE INCLUDE A FRONT AND SIDE
 ELEVATION VIEW THAT SHOWS THE BURIAL DEPTH, ANCHORING
 BASE MATERIAL, AND THE TYPES, SIZES, AND NUMBERS OF
 ANCHORS, CABLES OR STRAPS, AND THE TYPE OF PROTECTIVE
 SLEEVES FOR THE CABLES OR STRAPS. PLEASE PROVIDE A
 COMPLETE DETAIL THAT INCLUDES THE ATTACHMENT OF THE
 DOME AND COVER.
  
 B) FAILED. SHOW HOW THE TANK WILL BE PROTECTED AGAINST
 CORROSION BY INSTALLATION OF A CATHODIC PROTECTION
 SYSTEM CONSISTING OF A SACRIFICIAL ANODE OR AN
 IMPRESSED CURRENT ANODE PER SECTIONS 5.2.1.11 & 6.6.6.1
 (1) NFPA 58. INDICATE THE TYPE OF PROTECTION AND HOW IT
 WILL BE TESTED- SECTION 6.17.1. DETAIL FOR ANODE BAG
 INSTALLATION NOT PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  