Plan Review Notes
Plan Review Notes For Permit 20100012
Permit Number 20100012
Review Stop G
Sequence Number 1
Notes
Date Text
2020-10-26 14:06:411ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20100012
 10/26/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SURVEY: INDICATE THE REQUIRED 10 FT. CLEARANCE
 DISTANCE FOR THE UG TANK TO THE DRIVEWAY- SECTION
 6.6.6.1(B) & (C) NFPA 58-14. TANKS INSTALLED WITH 10
 FT. SHALL BE INSTALLED 18 IN. BELOW GRADE OR VEHICLE
 PROTECTION SHALL BE PROVIDED.
  
 2) SURVEY: CORRECT THE 5 FT. GENERATOR EXHAUST
 CLEARANCE TO OPENINGS INTO THE BUILDING. A 10 FT.
 CLEARANCE IS REQUIRED TO MECHANICAL AND GRAVITY AIR
 INTAKES INTO THE BUILDING PER SECTION R303.5.1 FBC RES.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 500-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE
 BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED)
 IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE
 REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN
 SECTION 5.2.1.1 NFPA 58.
  
 4) PROVIDE LP TANK INSTALLATION DETAILS AS REQUIRED BY
 NFPA 58:
 A) ENGINEERING FOR ANCHORING THE TANK TO PREVENT
 FLOTATION, COLLAPSE, OR LATERAL MOVEMENT- SECTION
 6.6.1.6. PLEASE INCLUDE A FRONT AND SIDE ELEVATION VIEW
 THAT SHOWS THE BURIAL DEPTH, ANCHORING BASE MATERIAL,
 AND THE TYPES, SIZES, AND NUMBERS OF ANCHORS, CABLES OR
 STRAPS, AND THE TYPE OF PROTECTIVE SLEEVES FOR THE
 CABLES OR STRAPS.
 B) SHOW HOW THE TANK WILL BE PROTECTED AGAINST
 CORROSION BY INSTALLATION OF A CATHODIC PROTECTION
 SYSTEM CONSISTING OF A SACRIFICIAL ANODE OR AN
 IMPRESSED CURRENT ANODE PER SECTIONS 5.2.1.11 & 6.6.6.1
 (1) NFPA 58. INDICATE THE TYPE OF PROTECTION AND HOW IT
 WILL BE TESTED- SECTION 6.17.1
  
 5) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING
 SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1
 WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  