Plan Review Notes For Permit 20091356 |
Permit Number |
20091356 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-10-20 17:21:03 | 1ST REVIEW FBC-2017 RES. FUEL GAS | | PERMIT- 20091356 | | 10/20/2020 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SUBMIT HIGHLIGHTED OR MARKED UP SPECS FOR THE | | GENERATOR INDICATING THE FULL LOAD CAPACITY OF THE | | GENERATOR AND THE INPUT PRESSURE- SECTION 107.2.1 WPB | | AND G2413.2 FBC RES. | | | | 2) INDICATE ON THE RISER THE MAKE AND MODEL OF THE | | REGULATOR AND THE OUTLET PRESSURE- SECTION G2421.1 & | | G2421.2. SUBMIT MARKED UP OR HIGHLIGHTED SPECS SHOWING | | THE SELECTED MODEL, THE MAX INLET AND OUTLET SIZE AND | | PRESSURES, SPRING DATA, AND ORIFICE SIZE. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|