2020-10-01 15:02:55 | 1ST REVIEW FBC-2017 PLUMBING |
| PERMIT- 200901355 |
| 10/1/2020 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS A4.2.1: THE ACCESSIBLE CAFE SINK WAS DESIGNED |
| FOR A PARALLEL APPROACH UNDER MASTER PERMIT 20050806 |
| AND KNEE AND TOE CLEARANCES FOR A FORWARD APPROACH WERE |
| NOT PROVIDED ON THE MASTER PLAN- SHEETS A0.04 & A4.21. |
| PLEASE PROVIDE A DETAIL PER SECTIONS 606.2 AND 306.1 |
| FBC ACC. |
| |
| 2) TP6: NEW DRAIN PENETRATIONS OF THE EXISTING SLAB MAY |
| REQUIRE AN X-RAY TO LOCATE REINFORCING STEEL OR POST |
| STRESSED FLOOR TENDONS. PLEASE PLACE A NOTE ON THE |
| PLANS TO VERIFY COMPLIANCE WILL BE MET- SECTION 107.2.1 |
| WPB. |
| |
| 3) TP6: NEW DRAIN PIPE PENETRATIONS OF THE EXISTING |
| SLAB WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR |
| SPACE AROUND THE PIPING. PROVIDE A UL TESTED AND |
| APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- |
| SECTION 714.4.1.2 FBC B. |
| |
| 4) TP6: PLEASE INDICATE THE CODE SECTIONS YOU ARE |
| REFERENCING IN NOTE #4 ABOUT NOT PROVIDING THE TRAP |
| PRIMER, AND THE INSULATION OF THE ICE MAKER DRAIN IN |
| MULTI-STORY BUILDINGS. HAT YOU ARE USING IN REFERENCE |
| TO NOTE #4- SECTION 107.2.1 WPB. IN ACCORDANCE WITH |
| SECTION 1002.4.1 FBC P IT APPEARS A TRAP PRIMER IS |
| REQUIRED. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |