2020-10-04 16:21:14WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20091255
 ADD: 1801 S FLAGLER DR. # 1210
 CONT: AT YOUR SERVICE WINDOWS & DOORS
 TEL: 561-846-2378
 E-MAIL: JOHN@ AYSWINDOWS.COM
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. OCT. 12TH/ 2020
 ACTION: DENIED
  
 1) SEMI COMPLIED, CONTRACTOR SIGNED THEIR NAME AND
 LICENSE NUMBER BUT DIDNOT PRINT THEIR NAME ON THE FLOOR
 PLAN. THE CONTRACTOR FAILED TO SIGN, NOR PRINT THEIR
 NAME AND LICENSE NUMBER ON THE PRODUCT APPROVAL REVIEW
 FORM, THIS DOCUMENT IS ALSO PART OF THE CONTRACTORS
 DESIGN AS FAR AS TYPES OF GLAZING UNITS, SIZE AND
 ASSOCIATED PRESSURES.
 1ST ROUND OF COMMENTS. PLEASE NOTE THE SUBMITTED FLOOR
 PLAN NEEDS TO HAVE THE QUALIFIER/ CERTIFICATE HOLDER
 PRINT THEIR NAME, SIGN THEIR NAME AND LICENSE NUMBER ON
 ALL OF THEIR DRAWINGS. CERTIFICATION BY CONTRACTOR.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 2) COMPLIED. THE SUBMITTED FLOOR PLAN DOES NOT SHOW THE
 LOCATION OF THE UNIT COMPARED TO THE OVERALL BUILDING
 FLOOR PLAN, CANNOT DETERMINE IF THE UNIT IS IN WALL
 ZONE 4 OR WALL ZONE 5. PRESSURES WILL DIFFER GREATLY.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. 2017
 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 3) 2ND REVIEW. THE SINGLE HUNG WINDOWS AND MULLIONS
 WERE NOT IDENTIFIED, THE PLAN REVIEWER CIRCLED OPENING
 SIZES AND ASSOCIATED PRESURES ALL GLAZING TYPES WORKED.
 THE SLIDING GLASS DOORS NOTHING WAS IDENTIFIED. WHEN
 REVIEWING THESE OPENINGS USING THE INFROMATION FROM THE
 PRODUCT APPROVAL FORM AND THE DESIGN PRRESSURE CHART
 THE PRODUCT APPROVAL FL. 18321-R2 PAGE 3/23 INDICATES
 REGAURDLESS OF PANEL SIZE (UNKNOWN CONTRACTOR GAVE THE
 OVERALL SIZE OF THE OPENING, SLIDING GLASS DOORS ALWAYS
 USE PANEL SIZE BECAUSE OF THE INTERLOCK BETWEEN
 PANELS/ DOORS ACTS AS A MULLION) THE HEIGHT IS KNOWN 96
 INCHES AND FOR BOTH THE STANDARD ASTRICAL AND HEAVY
 DUTY LIMIT THE PRESSURE TO 60.0 PSF. THE SUBMITTED
 PRODUCT APPROVAL FORM 1 SHOWED THE PRODUCT
 REQUIRED-62.8 PSF BUT THE APPROVAL IS GOOD FOR ONLY =/-
 60.00 PSF. THE 2ND PRODUCT APPROVAL REVIEW FORM THE NOA
 DESIN PRESSURE VALUES WERE INCREASED TO +/- 80 PSF
 WHICH ARE HIGHER THAN THE REQUIRD DESIGN PRESSURES, BUT
 THE PRODUCT APPROVAL SUBMITTED ATECHNICAL SHEETS STILL
 SHOW =/- 60.00PSF.PLEASE REVIEW WITHIN THE SAME PRODUCT
 APPROVAL SYSTEM 18321.1 SERIES 600 KM IS GOOD FOR
 +90/-110 PSF. IF THE CONTRACTOR WISHES TO INSTALL THIS
 UNIT THE TESTING REPORTS (EVALUATION) AND INSTALLATION
 INSTRUCTIONS WOULD NEED TO BE UPLOADED AND IDENTIFY
 OPENING SIZE, PRESSURES, TPYE OF ASTRICAL, POSSIBLE
 GLAZING TYPE!!!
  
 1ST ROUND OF COMMENTS. NONE OF THE SUBMITTED PRODUCT
 APPROVALS IDENTIFY THE TYPE OF GLASS, SIZE OF GLAZING,
 MULLIONS AND ASSOCIATED PRESSURES.
 IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER