Plan Review Notes
Plan Review Notes For Permit 20091253
Permit Number 20091253
Review Stop B
Sequence Number 1
Notes
Date Text
2020-11-10 14:12:03JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 ALTERNATE: CONTACT PETER VALENTI (561) 805-6673
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC R 310.4. PROVIDE A COMPLETE SET OF FLOOR
 PLANS/BUILDING FOOTPRINT SHOWING LOCATION OF PROPOSED
 ACCORDION SHUTTERS TO BE INSTALLED, SHOW REQUIRED MEANS
 OF ESCAPE. INCLUDE ROOM DESIGNATION.
 2. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF
 PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN
 HEADING ?SHUTTER INSTALLED? SHUTTERS ARE INSTALLED
 VERTICALLY AS PER SHEET 2 OF FL16893 R-5.
  