2020-10-14 09:01:01 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20091217 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M-1.0 NOTE 8 INDICATES THAT THE SUB-CONTRACTOR |
| IS TO TEST AND BALANCE THE AIR QUANTITIES TO THOSE ON |
| THE PLANS. PLEASE SHOW THE CFM?S ON THE PLANS FOR EACH |
| ROOM AND AREA. FBC M 403.3.1.5 |
| |
| 2) PLEASE PROVIDE AN OUTSIDE AIR CALCULATION FOR THIS |
| PROJECT. FBC M TABLE 403.3.1.1 |
| |
| 3) PLEASE SHOW THE DUCT AND DUCT SIZES FOR THIS |
| PROJECT. FBC 107.2.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |