2020-10-01 15:29:16 | 010/01/20 1ND PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. A SUB IRRIGATION PERMIT IS REQUIRED BY A LICENSED |
| CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 105.1. |
| |
| 2. PLEASE PROVIDE CALCULATIONS FOR STORM DRAIN SIZING |
| INCLUDING THE EXISTING THAT THE NEW DRAIN IS TO CONNECT |
| TO. INCLUDE THE IMPACT OF THE IRRIGATION SYSTEM ON THE |
| DRAINAGE SYSTEM. |
| |
| 3. PLEASE DETAIL OR PROVIDE SPECIFIC SPECIFICATION AND |
| TESTING STANDARDS IF CORRUGATED PIPE AND FITTINGS WILL |
| BE USED TO PECULATE WATER FROM PLANTER IN COMPLIANCE |
| WITH FBC PL TABLES 702.1 AND 702.4. |
| |
| 4. PLEASE PROVIVE WHERE ALL STORM DRAIN CONNECTIONS ARE |
| SHOWN ON THE SITE/CIVIL DRAWINGS PER THE WPB FBC |
| 107.2.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |