Plan Review Notes For Permit 20091213 |
Permit Number |
20091213 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-10-09 11:27:17 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-VERIFY HEADROOM CLEARANCE AT STAIR LANDING AREA AND | | SECOND FLOOR ABOVE. NEED 80 INCHES MIN. SEC. 1011.3 | | FBC-BUILDING. | | 2-VERIFY PLANTER HEIGHT TO COMPLY WITH THE BARRIER | | HEIGHT OF 27 INCHES AS REQUIRED BY SEC. 307.4 | | FBC-ACCESSIBILITY FOR REQUIRED VERTICAL CLEARANCE BELOW | | STAIRWAY. | | 3-) WELDED OR BOLTED CONNECTIONS | | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE | | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE | | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED | | STANDARDS AT TIME OF INSPECTION. | | 2017 FBC-B 2204.1 WELDING | | 1. WELD PROCEDURES SPECIFICATIONS | | 2) QUALIFICATIONS OF WELDING PERSONAL | | 2017 FBC-B 2204.2 BOLTING. | | |
|