2020-10-05 13:47:001ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20090781
 9/24/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE GENERATOR SPECS SUBMITTED UNDER PERMIT- 20060140
 SHOW A NATURAL GAS INPUT PRESSURE OF 3.5- 7 IN. W.C.
 FOR THE 22 KW GENERATOR, HOWEVER THE RISER DRAWING
 SHOWS A REGULATOR WITH A 11 IN. W.C DELIVERY PRESSURE.
 PLEASE CORRECT AND INDICATE THE MAKE AND MODEL OF THE
 SELECTED REGULATOR ON THE RISER. SUBMIT MARKED UP OR
 HIGHLIGHTED SPECS SHOWING THE MODEL, INLET AND OUTLET
 PRESSURES, SPRING SELECTION, AND ORIFICE SIZE- SECTION
 G2421.1 & G2421.2. SHOW THE REQUIRED PIPE UNIONS AT THE
 REGULATOR.
  
 2) PLEASE NOTE THE GENERATOR (UNDER SEPARATE PERMIT-
 20060140) SHALL BE INSTALLED A MINIMUM OF 5' AWAY FROM
 COMBUSTIBLE WALLS- SEC. 4.1.4 NFPA 37, AND A MINIMUM OF
 10' FROM MECHANICAL OR GRAVITY AIR INTAKES (WINDOW AND
 DOOR OPENINGS) INTO THE BUILDING- SEC. R303.5.1 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  