2023-04-24 10:21:24 | 3RD REVIEW FBC-2020 PLUMBING |
| PERMIT- 20091114 |
| 4/24/23 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE REVIEW THE BUILDING REVIEW COMMENTS AND NOTE |
| FINAL APPROVAL OF THE PLUMBING PLANS CANNOT BE |
| ACCOMPLISHED UNTIL THOSE ISSUES CONCERNING STATE |
| APPROVED PLANS AND SITE MODIFICATIONS ARE RESOLVED. |
| |
| 2) SHEETS P-1, P-2, & P-3: BASED ON SEC. 1003.3.2 FBC P |
| THE FOOD WASTE DISPOSER UNDER THE KITCHEN SINK SHALL |
| NOT DISCHARGE TO THE GREASE INTERCEPTOR. PROVIDE A |
| SOLIDS INTERCEPTOR OR REMOVE THE DISPOSER. THE SINKS |
| (S1 & S2 AND THE RELOCATED 3-COMPARTMENT SINK ON THE |
| EXTERIOR) ARE ALSO REQUIRE TO HAVE INDIRECT WASTE |
| RECEPTORS IF USED FOR FOOD HANDLING OR DISHWASHING- |
| SEC. 802.1 FBC P. |
| |
| 3) DUE TO A CHANGE IN PROCESS, THE GREASE INTERCEPTOR |
| PERMIT APPLICATION IS REQUIRED TO BE SUBMITTED PRIOR TO |
| FINAL APPROVAL OF THE PLUMBING PLAN REVIEW. YOU CAN |
| SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF YOU DO |
| NOT HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED |
| PERMIT APPLICATION TO [email protected] . YOU |
| WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. |
| YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT |
| THE APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND |
| THAT YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. |
| AFTER YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA |
| EMAIL AND I WILL CHANGE THE REVIEW STATUS TO PASS. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |