Plan Review Notes
Plan Review Notes For Permit 20091114
Permit Number 20091114
Review Stop P
Sequence Number 2
Notes
Date Text
2021-09-09 14:24:072ND REVIEW FBC-2020 PLUMBING
 PERMIT- 20091114
 9/9/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET SP-1: SHOW THE ACCESSIBLE ROUTE TO THE NEW
 DRINKING FOUNTAIN- SECTION 206.2.2 & 402.1 FBC ACC.
  
 2) A1, A5, A6: A CLEAR FLOOR SPACE DESIGNED FOR FORWARD
 APPROACH IS SHOWN AT SINK S-1 IN THE KITCHEN HOWEVER
 THE PLUMBING PLANS INDICATE THAT INDIRECT WASTE IS
 BEING PROVIDED. PLEASE PROVIDE A DETAIL SHOWING THE
 REQUIRED KNEE AND TOE CLEARANCES AT THE SINK- SEE
 FIGURES 306.2 & 306.3 FBC ACC.
  
 3) A1: THE WATER CLOSET 54-INCH CLEAR FLOOR SPACE
 DIMENSIONS MEASURED PERPENDICULAR FROM THE REAR WALLS
 IS INCORRECT- 56 INCHES MINIMUM REQUIRED- SECTION
 604.3.1 FBC ACC.
  
 4) A5: MISSING OR INCORRECT ACCESSIBILITY COMPLIANCE
 DETAILS PER FBC ACC.
  
 A) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS
 NOT PROVIDED- SECTION 604.2.
  
 B) THE REAR WATER CLOSET GRAB SHALL BE POSITIONED SO
 THE BAR WILL EXTEND A MINIMUM OF 12 INCHES FROM THE
 CENTERLINE OF THE WATER CLOSET TO THE ADJACENT WALL-
 SEE FIGURE 604.5.2. PLEASE CORRECT THE DETAIL.
  
 F) PROVIDE A DETAIL SHOWING THE KNEE AND TOE CLEARANCES
 FOR THE LAVATORIES- SECTION 606.2 AND FIGURES 306.2 &
 306.3.
  
 G) MEASUREMENTS HAVE NOT BEEN PROVIDED TO SHOW THE
 LOCATIONS OF SHOWER CONTROLS, FAUCETS, AND SPRAYERS-
 SECTION 608.5.2.
  
 I) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6.
 PLEASE ADD THE SHOWER SPRAY SPECIFICATIONS TO THE
 FIXTURE SCHEDULE- SECTION 608.6.
  
 5) A6: SHOW THE REQUIRED 1/4 INCH PER FT SLOPE FOR THE
 SHOWER PAN LINER- SECTION 417.5.2 FBC P.
  
 6) P1, P2, & P3: THE WASHING MACHINE IS REQUIRED TO
 DISCHARGE THROUGH AN INTERCEPTOR IN ACCORDANCE WITH
 SECTION 1003.6. PLEASE SHOW THE INTERCEPTOR ON THE
 DRAWINGS AND SUBMIT MANUFACTURER'S SPECIFICATIONS.
  
 7) P-3: THE HOT WATER RETURN CONNECTION TO THE
 THERMOSTATIC MIXING VALVE IS NOT SHOWN IN THE DETAIL-
 SECTION 607.2.2 FBC P.
  
 8) P-2, P-3: TEMPERED WATER IS REQUIRED AT THE LAVATORY
 SINKS IN ACCORDANCE WITH SECTION 419.5 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  