2021-04-13 16:10:02 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 20091114 |
| 4/13/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS P2 & P3: PROVIDE GREASE INTERCEPTOR SIZING |
| CALCULATIONS, AN ENLARGED PLUMBING PIPING DETAIL, AND |
| SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTIONS 1003.3.5 |
| FBC P. A) THE SAMPLING PORT DETAIL SHOWING A SANITARY |
| CROSS WITH SUMP WHICH IS NOT ACCEPTABLE. PLEASE PROVIDE |
| A SAMPLING PORT DETAIL IN ACCORDANCE WITH THE |
| MANUFACTURER'S SPECIFICATIONS. |
| |
| 2) P1: PLEASE PROVIDE A NOTE REQUIRING A FL. LICENSED |
| PLUMBING CONTRACTOR TO OBTAIN A SEPARATE PERMIT FOR |
| INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE |
| WITH SECTION 105.1 WPB AND SEC. 90-33 WPB CODE OF |
| ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY |
| THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION |
| BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB |
| UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR |
| FURTHER INFORMATION. |
| |
| 3) P1, P2, & P3: PROVIDE AN EQUIPMENT SCHEDULE AND |
| PLUMBING PIPING DETAILS FOR THE NEW DRINKING FOUNTAINS- |
| SECTIONS 107.2.1 & 107.3.5.3.1 WPB. |
| |
| 4) P1, P2, P3: SHOW THE LOCATION OF THE REQUIRED |
| SERVICE SINK AND PROVIDE AN EQUIPMENT SCHEDULE AND |
| PIPING DETAILS- TABLE 403.1 FBC P. |
| |
| 5) P2 & P3: PROVIDE THE SANITARY DRAIN AND VENT |
| CONNECTIONS, AND PIPING DETAILS FOR THE RELOCATED |
| 3-COMPARTMENT SINK- SECTIONS 107.2.1 & 107.3.5.3.1 WPB. |
| PLEASE CLARIFY THE USE OF THE SINK AND PROVIDE AN |
| INDIRECT WASTE DETAIL- SECTION 802.1.1 FBC P. |
| |
| 6) P-3: SHOW BACKFLOW PREVENTER LOCATIONS AT THE WATER |
| SUPPLY LINES TO THE INTERIOR AND EXTERIOR ICE MAKERS- |
| SECTION 608.3 FBC P. |
| |
| 7) P1: THE REQUIRED ENERGY COMPLIANCE REPORT HAS NOT |
| BEEN SUBMITTED. PROVIDE THE EFFICIENCY RATING OF THE |
| NEW WATER HEATER IN THE EQUIPMENT SCHEDULE, AND ENTER |
| THE DATA IN THE ENERGY COMPLIANCE REPORT- SEE SECTION |
| C101.5.1 & TABLE C404.2 FBC EC. |
| |
| 8) P0: PLEASE INCLUDE THE HOSE BIB IN THE PLUMBING |
| FIXTURE SCHEDULE- SECTION 608.16.4.2 FBC P. |
| |
| 9) A5 REQUIRED ACCESSIBILITY COMPLIANCE DETAILS- FBC |
| ACC: |
| |
| A) CENTERLINE OF THE WATER CLOSETS FROM THE SIDE WALLS- |
| SECTION 604.2. |
| B) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| FLOOR- SECTION 604.4. |
| C) HEIGHT OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| THE REFLECTIVE SURFACES- SECTION 603.3 |
| D) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| FIGURES 604. |
| E) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS - |
| SECTION 604.6. |
| F) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| 606.2 |
| G) LOCATIONS OF SHOWER CONTROLS, FAUCETS, AND SPRAYERS- |
| SECTION 608.5.2. |
| H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3.2. |
| I) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6. |
| PLEASE ADD THE SHOWER SPRAY SPECIFICATIONS TO THE |
| FIXTURE SCHEDULE- SECTION 608.6. |
| |
| 10) P3: PROVIDE A SHOWER PAN DETAIL- SECTION 421.5 FBC |
| P. |
| |
| 11) P2 & P3: MODIFY THE WATER HEATER DETAIL TO SHOW THE |
| REQUIRED DRAIN PAN, PAN DRAIN RUN AND TERMINATION |
| LOCATION- 504.7 FBC P. |
| |
| 12) P2: RELOCATE THE LOCATIONS OF THE WATER SHUT OFF |
| VALVES FROM BEHIND THE STACKABLE WASHER/DRYER TO A |
| LOCATION WITH ACCESS- SECTION 606.3 FBC P. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |