2020-12-31 07:58:11 | 1ST REVIEW FBC-2017 RES. |
| PERMIT- 20091047 |
| 12/31/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SUBMIT THE CORRECT MANUFACTURER'S SPECIFICATIONS FOR |
| THE 120-GALLON VERTICAL LP TANKS. THE SPECS SUBMITTED |
| ARE FOR HORIZONTAL-TYPE TANKS- SECTION 5.2.1.1 NFPA 58. |
| |
| 2) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| SHALL PROVIDE HIS/HER PRINTED NAME AND SIGNATURE ON IT- |
| SECTION 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) |
| & 471.025., AND SHALL ALSO PROVIDE THE ADDRESS OF THE |
| PROJECT. |
| |
| 3) PLEASE PLACE NOTES ON THE SITE PLAND SURVEY TO |
| INDICATE THE GENERATOR WILL BE INSTALLED A MIONIMUM OF |
| 10 FT. AWAY FROM MECHANICAL AND GRAVITY AIR INTAKES |
| INTO THE BUILDING- SECTION R303.5.1 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |