2020-10-14 10:27:54PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PRODUCT APPROVAL FOR THE CONCRETE ROOF TILE IS
 EXPIRED. NOA NO. 14-0408.06 EXPIRED ON 5/20/2019.
 SUBMIT CURRENT PRODUCT APPROVAL.CITY AMENDMENTS FBC
 107.3.4
  
 2) SPECIFY THE SLOPE OF THE AWNING ROOF. THE MINIMUM
 SLOPE FOR TILE ROOFS IS 2:12. FBCR905.3.7
  
 3)THE PLANS SPECIFY THAT THE LEDGER AND WALL BRACKET
 ARE BOLTED TO THE EXISTING WOOD WALL FRAMING. SPECIFY
 THE BOLT TYPE ( LAG BOLT) AND THE REQUIRED EMBED DEPTH
 INTO THE EXISTING WOOD FRAMING. CITY AMENDMENTS FBC 107
  
 4) THE PLANS SPECIFY THAT THE ROOF SHEATHING IS A 1/2"
 TONGUE AND GROOVE SYSTEM. PLEASE CLARIFY WHAT THIS IS.
 TILE ROOFS REQUIRE MORE THAN 1/2" SHEATHING WITH 24" OC
 RAFTER SPACING. CITY AMENDMENTS FBC 107.2.1
 NOTE. THE ROOFING NAILS USED FOR THE 30 # UNDERLAYMENT
 WILL BE EXPOSED ON THE UNDERSIDE OF THE ROOF DECK IF
 1/2" ROOF SHEATHING IS USED. FBC-R905.3.6 FASTENERS.
 REQUIRES THE FASTENERS TO PENETRATE THROUGH OR A
 MINIMUM OF 3/4" INTO THE SHEATHING.
  
 5) THE SPAN BETWEEN THE SUPPORT BRACKETS FOR THE 4X8
 BEAM CARRYING THE TILE ROOF APPEARS TO BE EXCESSIVE.
 PROVIDE SIGNED AND SEALED CALCULATIONS TO SHOW THE
 ALLOWABLE SPAN FOR THE 4X8 BEAM, CITY AMENDMENTS FBC
 107.2.1.2
  
 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.