2020-10-14 10:27:54 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE PRODUCT APPROVAL FOR THE CONCRETE ROOF TILE IS |
| EXPIRED. NOA NO. 14-0408.06 EXPIRED ON 5/20/2019. |
| SUBMIT CURRENT PRODUCT APPROVAL.CITY AMENDMENTS FBC |
| 107.3.4 |
| |
| 2) SPECIFY THE SLOPE OF THE AWNING ROOF. THE MINIMUM |
| SLOPE FOR TILE ROOFS IS 2:12. FBCR905.3.7 |
| |
| 3)THE PLANS SPECIFY THAT THE LEDGER AND WALL BRACKET |
| ARE BOLTED TO THE EXISTING WOOD WALL FRAMING. SPECIFY |
| THE BOLT TYPE ( LAG BOLT) AND THE REQUIRED EMBED DEPTH |
| INTO THE EXISTING WOOD FRAMING. CITY AMENDMENTS FBC 107 |
| |
| 4) THE PLANS SPECIFY THAT THE ROOF SHEATHING IS A 1/2" |
| TONGUE AND GROOVE SYSTEM. PLEASE CLARIFY WHAT THIS IS. |
| TILE ROOFS REQUIRE MORE THAN 1/2" SHEATHING WITH 24" OC |
| RAFTER SPACING. CITY AMENDMENTS FBC 107.2.1 |
| NOTE. THE ROOFING NAILS USED FOR THE 30 # UNDERLAYMENT |
| WILL BE EXPOSED ON THE UNDERSIDE OF THE ROOF DECK IF |
| 1/2" ROOF SHEATHING IS USED. FBC-R905.3.6 FASTENERS. |
| REQUIRES THE FASTENERS TO PENETRATE THROUGH OR A |
| MINIMUM OF 3/4" INTO THE SHEATHING. |
| |
| 5) THE SPAN BETWEEN THE SUPPORT BRACKETS FOR THE 4X8 |
| BEAM CARRYING THE TILE ROOF APPEARS TO BE EXCESSIVE. |
| PROVIDE SIGNED AND SEALED CALCULATIONS TO SHOW THE |
| ALLOWABLE SPAN FOR THE 4X8 BEAM, CITY AMENDMENTS FBC |
| 107.2.1.2 |
| |
| 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| CITY RE-SUBMITTAL FORM. |