Date |
Text |
2020-09-29 12:07:43 | 2ND REVIEW FBC-2017 RES. PLUMBING. |
| PERMIT-20091013 |
| 9/29/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS P-2 & P-3: THE SELECTED RHEEM RETEX-18 IS |
| UNDERSIZED FOR REQUIRED HOT WATER GPM FLOW TO THE |
| FIXTURES. THE MANUFACTURER'S TEMPERATURE RISE CHART FOR |
| THE SELECTED RHEEM RETEX-18 SHOWS A MAX 4.0 GPM FLOW AT |
| A 31-DEGREE F TEMPERATURE RISE. PLEASE NOTE HOT WATER |
| AT A TEMPERATURE OF 110 DEGREES F SHALL BE PROVIDED TO |
| THE FIXTURES WHERE REQUIRED- SECTION P2801.1 FBC RES. |
| REFER TO TABLE P2903.1 FBC P AND SELECT A WATER HEATER |
| WITH THE CAPACITY TO PROVIDE THE REQUIRED GPM HOT WATER |
| FLOW TO ALL FIXTURES AND APPLIANCES. INDICATE THE MAKE |
| AND MODEL ON THE CORRECTED PLANS AND SUBMIT |
| MANUFACTURER'S SPECIFICATIONS THAT INCLUDE THE |
| TEMPERATURE RISE CHART. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |