2020-09-29 12:07:432ND REVIEW FBC-2017 RES. PLUMBING.
 PERMIT-20091013
 9/29/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P-2 & P-3: THE SELECTED RHEEM RETEX-18 IS
 UNDERSIZED FOR REQUIRED HOT WATER GPM FLOW TO THE
 FIXTURES. THE MANUFACTURER'S TEMPERATURE RISE CHART FOR
 THE SELECTED RHEEM RETEX-18 SHOWS A MAX 4.0 GPM FLOW AT
 A 31-DEGREE F TEMPERATURE RISE. PLEASE NOTE HOT WATER
 AT A TEMPERATURE OF 110 DEGREES F SHALL BE PROVIDED TO
 THE FIXTURES WHERE REQUIRED- SECTION P2801.1 FBC RES.
 REFER TO TABLE P2903.1 FBC P AND SELECT A WATER HEATER
 WITH THE CAPACITY TO PROVIDE THE REQUIRED GPM HOT WATER
 FLOW TO ALL FIXTURES AND APPLIANCES. INDICATE THE MAKE
 AND MODEL ON THE CORRECTED PLANS AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS THAT INCLUDE THE
 TEMPERATURE RISE CHART.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  