Plan Review Notes For Permit 20091013 |
Permit Number |
20091013 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-10-03 12:43:08 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | 1) FBC B 107.2.1, PLEASE PROVIDE A CLEAR CONNECTION | | DETAIL FOR THE STAIR LANDING AREA INCLUDING STAIR | | LANDING, BEAM 10 AND BEAM 11 CONNECTIONS. | | | | 2) FBC B 107.2.1, PLEASE PROVIDE NEW TRUSS TO STRUCTURE | | CONNECTION AND BRACING DETAILS.THIS INFORMATION IS | | REQUIRED TO BE PART OF THIS PLAN. | | NOTE: THE REQUIRED TRUSS ENGINEERING, WHICH IS | | SEPARATE, IS TO BE SUBMITTED ON THE JOB-SITE TO THE | | CITY INSPECTOR AND MUST BE SIGNED AND SEALED BY THE | | TRUSS ENGINEER AND REVIEW STAMP APPROVED BY THE | | DESIGNER OF RECORD FOR THIS PROJECT. | | | | 3) FBC B 107, PLEASE PROVIDE THE WINDOW MULLION PRODUCT | | APPROVALS. |
|