Notes
Date Text
2020-10-03 12:43:08PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 1) FBC B 107.2.1, PLEASE PROVIDE A CLEAR CONNECTION
 DETAIL FOR THE STAIR LANDING AREA INCLUDING STAIR
 LANDING, BEAM 10 AND BEAM 11 CONNECTIONS.
  
 2) FBC B 107.2.1, PLEASE PROVIDE NEW TRUSS TO STRUCTURE
 CONNECTION AND BRACING DETAILS.THIS INFORMATION IS
 REQUIRED TO BE PART OF THIS PLAN.
 NOTE: THE REQUIRED TRUSS ENGINEERING, WHICH IS
 SEPARATE, IS TO BE SUBMITTED ON THE JOB-SITE TO THE
 CITY INSPECTOR AND MUST BE SIGNED AND SEALED BY THE
 TRUSS ENGINEER AND REVIEW STAMP APPROVED BY THE
 DESIGNER OF RECORD FOR THIS PROJECT.
  
 3) FBC B 107, PLEASE PROVIDE THE WINDOW MULLION PRODUCT
 APPROVALS.