Plan Review Notes
Plan Review Notes For Permit 20091012
Permit Number 20091012
Review Stop B
Sequence Number 2
Notes
Date Text
2020-11-04 10:45:35WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20091012
 ADD: 1683 FORUM PLACE
 CONT: HALLMARK CONSTRUCTION
 TEL: 561-586-7664
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. NOV. 04TH/ 2020
 ACTION: DENIED
 4X FEE / NOTICE LONLY!!!! FLORIDA STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 NO TRANSMITTAL LETTER WAS SUBMITTED. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
  
 1) SHEET A-1:
 1A) 2ND REQUEST. UNDER THE HEADING APPLICABLE CODES &
 BUILDING CLASSIFICATION THE PLAN STATES IT IS AN
 INTERIOR ALTERATION LEVEL 2. UNDER THE HEADING TENANT
 INFORMATION FOR NEW TENANT SPACE # 1683 THE PLAN STATES
 THE PREVIOUS TENANT WAS OCCUPIED BY THE SPICE,
 RESTAURANT AN A-2 OCCUPANCY. THE NEW OCCUPANCY IS TO BE
 A CHIROPRACTIC OFFICE A BUSINESS OCCUPANCY. PLEASE NOTE
 THAT INSTEAD OF A LEVEL 2 ALTERATION THE EXIST.
 BUILDING CODE WOULD LIST THIS PLAN AS A CHANGE OF
 OCCUPANCY PLEASE REVIEW IN THE 2017 EXIST. BUILD. CODE
 SECTION 1001.2.2.1 PARTIAL CHANGE OF OCCUPANCY. PLEASE
 UPDATE THE PLANS.
  
 1B) 2ND REQUEST. ACCESSIBILITY DETAILS, THE FLOOR PLAN
 OF THE ACCESSIBLE RESTROOMS WITH A INSWING DOOR OF THE
 RESTROOMS, SWINGING IN OVER THE REQUIRED FLOOR SPACE OF
 THE LAV AND WATER CLOSET. 2017 FBC-ACCESSIBILITY CODE
 FIGURE 604.8.1.6 SHOWS AN OUTSWING DOOR. PLEASE ALSO
 REVIEW SECTION 603.2.3 DOOR SWING AND EXCEPTION 2. I
 BELIEVE THIS IS HOW YOU ARE STRIVING TO SHOW CODE
 COMPLIANCE. WHAT IS MISSING IS THE REQUIRED CLEAR FLOOR
 SPACE 30X48 BEYOND THE ARC OF THE DOOR. IT IS USUALLY
 SHOWN AT A 45-DEGREE ANGLE TO THE ENTRY DOOR.
  
 1C) 2ND REQUEST. GRAB BARS ARE SHOWN WITH THE
 MEASUREMENT TAKEN FROM FINISH FLOOR TO CENTERLINE OF
 THE GRAB BAR. 2017 FBC-ACCESSIBILITY CODE SECTION 609.4
 POSITION OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN
 A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, NOT CENTERLINE.
  
 1D) 2ND REVIEW. MISSING IS A SIDE WALL VIEW OF THE REST
 ROOM THE TOILET PAPER HOLDER LOCATION, DISTANCE FROM
 THE FRONT OF THE WATER CLOSET. TOILET PAPER DISPENSERS.
 ACCESS. CODE 604.7. THE TOILET PAPER DISPENSER SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM TO 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 1E) 2ND REVIEW. THE BACK WALL SHOWS A FRAMED MIRROR. IT
 APPEARS THE MEASUREMENT FROM THE FINISH FLOOR IS TO THE
 BOTTOM OF THE MIRRORS FRAME NOT THE REFLECTIVE SURFACE
 OF THE MIRROR. 603.3 MIRRORS. 2017 FBC-ACCESSIBILITY
 CODE. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 1F) 2ND REVIEW. PLEASE NOTE ON THE REAR WALL THERE IS A
 STATEMENT EPOXY PAINT ALL SIDES AS SELECTED BY TENANT.
 FBC-B 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET
 WALLS SHALL COMPLY WITH 1210.2.
  
 FBC-B1210.2. FINISH MATERIALS. WALLS, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
  
  
 PLEASE NOTE!!! 2017 FBC-B 1210.2.2. WALLS & PARTITIONS.
 THIS COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION. IN RESTROOMS EPOXY PAINT IS NO LONGER
 CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE.
 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT
 IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 1G) 2ND REVIEW. PLEASE NOTE IN BOTH DETAILS STAFF
 CABINET ELEV. 1 AND IN EXAM CABINET ELEV. 2 BOTH THE
 SINKS ARE AT A ELEVATION 34 INCHES BUT THE COUNTER TOP
 IN THE NEXT ADJOINING CABINETRY, THE COUNTERTOP IS 36
 INCHES IN HEIGHT. THE 2017 FBC-ACCESS. CODE SECTION
 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28
 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 1H) 2ND REVIEW. THE FLOOR PLAN FOR BOTH THE STAFF SINK
 AND EXAM ROOM SINK DOES NOT INDICATE THE CLEAR FLOOR
 SPACE REQUIRED. 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305, POSITIONED FOR A FORWARD
 APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING WITH 306
 SHALL BE PROVIDED, SEE EXCEPTIONS ALSO, BUT SHOW THE
 REQUIRED CLEAR FLOOR SPACE ON THE FLOOR PLAN.
 1I) 2ND REVIEW. THE LIFE SAFETY FLOOR PLAN SHOWS AN
 RECEPTIONIST DESK BUT THERE ARE NO DETAILS SHOWING THE
 HEIGHT OF THE COUNTER TOP AND WITH THE ACCESSIBLY
 REQUIREMENTS.
 CHECK WRITING SURFACES. 2017 ACCESS. CODE 904.3.3 CHECK
 WRITING SURFACES. WHERE PROVIDED, CHECK WRITING
 SURFACES SHALL COMPLY WITH 902.3. 902.3HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 SHOW COMPLIANCE WITH THE ACCESS. CODE 305.5 POSITION.
 UNLESS OTHERWISE SPECIFIED, CLEAR FLOOR OR GROUND SPACE
 SHALL BE POSITIONED FOR EITHER A FORWARD OR PARALLEL
 APPROACH TO AN ELEMENT.
  
 1J) 2ND REVIEW. THE LIFE SAFETY PLAN SHOWS EXIT LIGHTS
 AT BOTH THE FRONT AND REAR OF THE BUILDING, BUT THE
 PLAN DOES NOT INDICATE IF THESE EXITS ARE ACCESSIBLE?
 ACCESS. CODE 404.2.5. THRESHOLDS. THRESHOLDS, IF
 PROVIDED AT DOORWAYS, SHALL BE? INCH HIGH MAXIMUM.
 RAISED THRESHOLDS AND CHANGES IN LEVEL AT DOORWAYS
 SHALL COMPLY WITH 302 & 303.
  
 2)2ND REVIEW. DEMOLITION PLAN: THE DEMOLITION PLAN FOR
 THE ROOF INDICATES TO ABANDON AND CAP OFF ROOF
 EQUIPMENT CURBS. NO DETAILS PROVIDED FOR THE CONTRACTOR
 TYPE OF MATERIAL, THICKNESS OF MATERIAL AND SIZE AND
 SPACING OF THE FASTENERS TO ANCHOR THE NEW COVER TO THE
 CURB. 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  