2020-11-04 10:45:35 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20091012 |
| ADD: 1683 FORUM PLACE |
| CONT: HALLMARK CONSTRUCTION |
| TEL: 561-586-7664 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: WED. NOV. 04TH/ 2020 |
| ACTION: DENIED |
| 4X FEE / NOTICE LONLY!!!! FLORIDA STATUTE 553.80(2)(B) |
| WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| |
| NO TRANSMITTAL LETTER WAS SUBMITTED. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| |
| 1) SHEET A-1: |
| 1A) 2ND REQUEST. UNDER THE HEADING APPLICABLE CODES & |
| BUILDING CLASSIFICATION THE PLAN STATES IT IS AN |
| INTERIOR ALTERATION LEVEL 2. UNDER THE HEADING TENANT |
| INFORMATION FOR NEW TENANT SPACE # 1683 THE PLAN STATES |
| THE PREVIOUS TENANT WAS OCCUPIED BY THE SPICE, |
| RESTAURANT AN A-2 OCCUPANCY. THE NEW OCCUPANCY IS TO BE |
| A CHIROPRACTIC OFFICE A BUSINESS OCCUPANCY. PLEASE NOTE |
| THAT INSTEAD OF A LEVEL 2 ALTERATION THE EXIST. |
| BUILDING CODE WOULD LIST THIS PLAN AS A CHANGE OF |
| OCCUPANCY PLEASE REVIEW IN THE 2017 EXIST. BUILD. CODE |
| SECTION 1001.2.2.1 PARTIAL CHANGE OF OCCUPANCY. PLEASE |
| UPDATE THE PLANS. |
| |
| 1B) 2ND REQUEST. ACCESSIBILITY DETAILS, THE FLOOR PLAN |
| OF THE ACCESSIBLE RESTROOMS WITH A INSWING DOOR OF THE |
| RESTROOMS, SWINGING IN OVER THE REQUIRED FLOOR SPACE OF |
| THE LAV AND WATER CLOSET. 2017 FBC-ACCESSIBILITY CODE |
| FIGURE 604.8.1.6 SHOWS AN OUTSWING DOOR. PLEASE ALSO |
| REVIEW SECTION 603.2.3 DOOR SWING AND EXCEPTION 2. I |
| BELIEVE THIS IS HOW YOU ARE STRIVING TO SHOW CODE |
| COMPLIANCE. WHAT IS MISSING IS THE REQUIRED CLEAR FLOOR |
| SPACE 30X48 BEYOND THE ARC OF THE DOOR. IT IS USUALLY |
| SHOWN AT A 45-DEGREE ANGLE TO THE ENTRY DOOR. |
| |
| 1C) 2ND REQUEST. GRAB BARS ARE SHOWN WITH THE |
| MEASUREMENT TAKEN FROM FINISH FLOOR TO CENTERLINE OF |
| THE GRAB BAR. 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 |
| POSITION OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN |
| A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES |
| MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| THE GRIPPING SURFACE, NOT CENTERLINE. |
| |
| 1D) 2ND REVIEW. MISSING IS A SIDE WALL VIEW OF THE REST |
| ROOM THE TOILET PAPER HOLDER LOCATION, DISTANCE FROM |
| THE FRONT OF THE WATER CLOSET. TOILET PAPER DISPENSERS. |
| ACCESS. CODE 604.7. THE TOILET PAPER DISPENSER SHALL |
| COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM TO 9 |
| INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| THE CENTERLINE OF THE DISPENSER. |
| |
| 1E) 2ND REVIEW. THE BACK WALL SHOWS A FRAMED MIRROR. IT |
| APPEARS THE MEASUREMENT FROM THE FINISH FLOOR IS TO THE |
| BOTTOM OF THE MIRRORS FRAME NOT THE REFLECTIVE SURFACE |
| OF THE MIRROR. 603.3 MIRRORS. 2017 FBC-ACCESSIBILITY |
| CODE. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS |
| SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE |
| REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND. |
| |
| 1F) 2ND REVIEW. PLEASE NOTE ON THE REAR WALL THERE IS A |
| STATEMENT EPOXY PAINT ALL SIDES AS SELECTED BY TENANT. |
| FBC-B 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET |
| WALLS SHALL COMPLY WITH 1210.2. |
| |
| FBC-B1210.2. FINISH MATERIALS. WALLS, FLOORS AND |
| PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH |
| SECTIONS 1210.1 THROUGH 1210.4. |
| |
| |
| |
| PLEASE NOTE!!! 2017 FBC-B 1210.2.2. WALLS & PARTITIONS. |
| THIS COMMENT IS A RESULT OF THE BUILDING OFFICIAL |
| INTERPRETATION. IN RESTROOMS EPOXY PAINT IS NO LONGER |
| CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE. |
| WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, |
| URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4 |
| FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS, |
| THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT |
| IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| |
| 1G) 2ND REVIEW. PLEASE NOTE IN BOTH DETAILS STAFF |
| CABINET ELEV. 1 AND IN EXAM CABINET ELEV. 2 BOTH THE |
| SINKS ARE AT A ELEVATION 34 INCHES BUT THE COUNTER TOP |
| IN THE NEXT ADJOINING CABINETRY, THE COUNTERTOP IS 36 |
| INCHES IN HEIGHT. THE 2017 FBC-ACCESS. CODE SECTION |
| 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28 |
| INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND. |
| |
| 1H) 2ND REVIEW. THE FLOOR PLAN FOR BOTH THE STAFF SINK |
| AND EXAM ROOM SINK DOES NOT INDICATE THE CLEAR FLOOR |
| SPACE REQUIRED. 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR |
| SPACE COMPLYING WITH 305, POSITIONED FOR A FORWARD |
| APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 |
| SHALL BE PROVIDED, SEE EXCEPTIONS ALSO, BUT SHOW THE |
| REQUIRED CLEAR FLOOR SPACE ON THE FLOOR PLAN. |
| 1I) 2ND REVIEW. THE LIFE SAFETY FLOOR PLAN SHOWS AN |
| RECEPTIONIST DESK BUT THERE ARE NO DETAILS SHOWING THE |
| HEIGHT OF THE COUNTER TOP AND WITH THE ACCESSIBLY |
| REQUIREMENTS. |
| CHECK WRITING SURFACES. 2017 ACCESS. CODE 904.3.3 CHECK |
| WRITING SURFACES. WHERE PROVIDED, CHECK WRITING |
| SURFACES SHALL COMPLY WITH 902.3. 902.3HEIGHT. |
| THE TOPS OF WORK SURFACES SHALL BE 28 INCHES (710 MM) |
| MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND. |
| SHOW COMPLIANCE WITH THE ACCESS. CODE 305.5 POSITION. |
| UNLESS OTHERWISE SPECIFIED, CLEAR FLOOR OR GROUND SPACE |
| SHALL BE POSITIONED FOR EITHER A FORWARD OR PARALLEL |
| APPROACH TO AN ELEMENT. |
| |
| 1J) 2ND REVIEW. THE LIFE SAFETY PLAN SHOWS EXIT LIGHTS |
| AT BOTH THE FRONT AND REAR OF THE BUILDING, BUT THE |
| PLAN DOES NOT INDICATE IF THESE EXITS ARE ACCESSIBLE? |
| ACCESS. CODE 404.2.5. THRESHOLDS. THRESHOLDS, IF |
| PROVIDED AT DOORWAYS, SHALL BE? INCH HIGH MAXIMUM. |
| RAISED THRESHOLDS AND CHANGES IN LEVEL AT DOORWAYS |
| SHALL COMPLY WITH 302 & 303. |
| |
| 2)2ND REVIEW. DEMOLITION PLAN: THE DEMOLITION PLAN FOR |
| THE ROOF INDICATES TO ABANDON AND CAP OFF ROOF |
| EQUIPMENT CURBS. NO DETAILS PROVIDED FOR THE CONTRACTOR |
| TYPE OF MATERIAL, THICKNESS OF MATERIAL AND SIZE AND |
| SPACING OF THE FASTENERS TO ANCHOR THE NEW COVER TO THE |
| CURB. 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |