2020-10-09 09:50:22 | 1) SHT. A.1 - H.C.T.R. DETAIL PLAN - NOTES #1 & #3 - |
| THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| GRIPPING SURFACE PER FBC-ACCESS. SEC. 609.4. REVISE THE |
| NOTES. |
| 2) THE TOILET PAPER DISPENSERS SHALL BE LOCATED 7-9 |
| INCHES IN FRONT OF THE WATER CLESET MEASURED TO THE |
| CENTERLINE OF THE DISPENSER PER FBC-ACCESS. SEC. 604.7. |
| 3) SHT. A.1 - H.C.T.R. DETAIL - THE DOORS SHALL NOT |
| SWING INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED |
| FOR ANY FIXTURE PER FBC-ACCESS. SEC.603.2.3. (SEE |
| EXCEPTION #2). |
| 4) SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE STAFF |
| AND EXAM SINK PER FBC-ACCESS.SEC.606.2. A MINIMUM 30 |
| INCH WIDE CLEAR FLOOR SPACE COMPLYING WITH |
| FBC-ACCESS.SEC. 305 POSITIONED FOR A FORWARD APPROACH, |
| SHALL BE PROVIDED FOR THE EXAM ROOM SINK. A PARALLEL |
| APPROACH COMPLYNG WITH SEC. 305 SHALL BE PERMITTED TO |
| THE STAFF ROOM SINK. |
| 5) EPOXY PAINT ON THE TOILET ROOM WALLS DOES NOT COMPLY |
| WITH FBC-BUILDING SEC.12110.2.2. WALLS AND PARTITIONS |
| WITHIN 2 FEET (610 MM) OF SERVICE SINKS, URINALS AND |
| WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT |
| SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET (1219 MM) |
| ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, |
| THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE |
| THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. THE WALLS |
| AROUND THE JANITOR SINK SHALL ALSO COMPLY. |
| 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| TANKLESS WATER HEATERS. WPB AMEND. TO FBC SEC. 107.2.1. |
| 7) TEMPERED WATER IS REQUIRED AT THE LAVATORIES IN THE |
| TOILET ROOMS PER FBC-PLUMBING SEC.416.5.TEMPERED WATER |
| SHALL BE DELIVERED THROUGH AN APPROVED |
| WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| 1070 OR CSA B125.3. |
| 8) SIZE THE DRAINS FOR THE STAFF AND EXAM SINKS ON THE |
| SANITARY RISER. WPB AMEND. TO FBC SEC. 107.2.1. |
| 9) ONLY THE PLUMBING FIXTURES WITHIN THE BATHROOM GROUP |
| ARE PERMITTED TO BE VENTED BY A HORIZONTAL WET VENT PER |
| FBC-PLUMBING SEC.912.1. AS DRAWN, THE SANITARY RISER |
| DIAGRAM DOES NOT COMPLY. |
| 10) THE RISER DIAGRAM REFERS TO THE USE OF OFFSET |
| FLANGES.THESE FLANGES CANNOT BE USED PER FBC-PLUMBING |
| SEC.706.2. |
| 11) SHOW THE SIZE OF THE EXISTING SANITARY DRAIN |
| PIPING. WPB AMEND. TO FBC SEC. 107.2.1. |
| |