2020-10-09 09:50:221) SHT. A.1 - H.C.T.R. DETAIL PLAN - NOTES #1 & #3 -
 THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE PER FBC-ACCESS. SEC. 609.4. REVISE THE
 NOTES.
 2) THE TOILET PAPER DISPENSERS SHALL BE LOCATED 7-9
 INCHES IN FRONT OF THE WATER CLESET MEASURED TO THE
 CENTERLINE OF THE DISPENSER PER FBC-ACCESS. SEC. 604.7.
 3) SHT. A.1 - H.C.T.R. DETAIL - THE DOORS SHALL NOT
 SWING INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED
 FOR ANY FIXTURE PER FBC-ACCESS. SEC.603.2.3. (SEE
 EXCEPTION #2).
 4) SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE STAFF
 AND EXAM SINK PER FBC-ACCESS.SEC.606.2. A MINIMUM 30
 INCH WIDE CLEAR FLOOR SPACE COMPLYING WITH
 FBC-ACCESS.SEC. 305 POSITIONED FOR A FORWARD APPROACH,
 SHALL BE PROVIDED FOR THE EXAM ROOM SINK. A PARALLEL
 APPROACH COMPLYNG WITH SEC. 305 SHALL BE PERMITTED TO
 THE STAFF ROOM SINK.
 5) EPOXY PAINT ON THE TOILET ROOM WALLS DOES NOT COMPLY
 WITH FBC-BUILDING SEC.12110.2.2. WALLS AND PARTITIONS
 WITHIN 2 FEET (610 MM) OF SERVICE SINKS, URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET (1219 MM)
 ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. THE WALLS
 AROUND THE JANITOR SINK SHALL ALSO COMPLY.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 TANKLESS WATER HEATERS. WPB AMEND. TO FBC SEC. 107.2.1.
 7) TEMPERED WATER IS REQUIRED AT THE LAVATORIES IN THE
 TOILET ROOMS PER FBC-PLUMBING SEC.416.5.TEMPERED WATER
 SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
 8) SIZE THE DRAINS FOR THE STAFF AND EXAM SINKS ON THE
 SANITARY RISER. WPB AMEND. TO FBC SEC. 107.2.1.
 9) ONLY THE PLUMBING FIXTURES WITHIN THE BATHROOM GROUP
 ARE PERMITTED TO BE VENTED BY A HORIZONTAL WET VENT PER
 FBC-PLUMBING SEC.912.1. AS DRAWN, THE SANITARY RISER
 DIAGRAM DOES NOT COMPLY.
 10) THE RISER DIAGRAM REFERS TO THE USE OF OFFSET
 FLANGES.THESE FLANGES CANNOT BE USED PER FBC-PLUMBING
 SEC.706.2.
 11) SHOW THE SIZE OF THE EXISTING SANITARY DRAIN
 PIPING. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW