Plan Review Notes For Permit 20090998 |
Permit Number |
20090998 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2020-11-10 17:44:39 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1- SHEET A4.2: | | A)DETAIL #16 RAMP AND STAIR DETAILS: NEED TO SHOW | | HANDRAIL ON BOTH SIDES OF STAIRS AND RAMPS. SEC. 505.2 | | FBC-ACCESSIBILITY. | | B)DETAIL #16 RAMP AND STAIR DETAILS: NEED TO SHOW THE | | TOP AND BOTTOM EXTENSION AT RAMP. AND PROVIDE DETAILS. | | SEC. 505.10.1 FBC-ACCESSIBILITY. | | C)DETAIL #14 AND DETAIL #17: THE BOTTOM EXTENSION AT | | STAIRS NEED TO EXTEND AT THE SLOPE OF THE STAIR FLIGHT | | AS REQUIRED BY SEC. 505.10.3 FBC-ACCESSIBILITY. | | | | 2- SHEET A4.3: | | A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE | | SIGNAGE WALL AND THE LOW WALL ALONG THE RAMPS. PROVIDE | | COMPLETE SPECS FOR FOOTINGS, INCLUDING SIZES | | REINFORCEMENT, ETC. AND WALL VERTICAL REINFORCEMENT. | | SEC. 1603.1 FBC-BUILDING. |
|