Plan Review Notes
Plan Review Notes For Permit 20090998
Permit Number 20090998
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-10-26 10:24:26THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEETS A11, A21, A 42, A43, DO NOT APPEAR TO
 INDICATE HANDRAILS ON BOTH SIDES OF THE STAIRS.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 7.2.2.4 GUARDS AND HANDRAILS.
 7.2.2.4.1 HANDRAILS.
 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON
 BOTH SIDES,
 UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR
 7.2.2.4.1.6.
  
 PLEASE REVIEW AND CORRECT.
  
  
 2) SHEET A21 - THE STAIRS BY THE DOUBLE DOORS DOES NOT
 APPEAR TO INDICATE RAILINGS ON BOTH SIDES BUT ALSO NO
 CENTER RAILING.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 7.2.2.4 GUARDS AND HANDRAILS.
 7.2.2.4.1 HANDRAILS.
 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON
 BOTH SIDES,
 UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR
 7.2.2.4.1.6.
 7.2.2.4.1.2 IN ADDITION TO THE HANDRAILS REQUIRED AT
 THE SIDES OF
 STAIRS BY 7.2.2.4.1.1, BOTH OF THE FOLLOWING PROVISIONS
 SHALL APPLY:
 (1) FOR NEW STAIRS, HANDRAILS SHALL BE PROVIDED WITHIN
 30 IN. (760
 MM) OF ALL PORTIONS OF THE REQUIRED EGRESS WIDTH.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  