Plan Review Notes For Permit 20090998 |
Permit Number |
20090998 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-10-26 10:24:26 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | 1) SHEETS A11, A21, A 42, A43, DO NOT APPEAR TO | | INDICATE HANDRAILS ON BOTH SIDES OF THE STAIRS. | | | | PER NFPA 101, CH 7 MEANS OF EGRESS | | | | 7.2.2.4 GUARDS AND HANDRAILS. | | 7.2.2.4.1 HANDRAILS. | | 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON | | BOTH SIDES, | | UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR | | 7.2.2.4.1.6. | | | | PLEASE REVIEW AND CORRECT. | | | | | | 2) SHEET A21 - THE STAIRS BY THE DOUBLE DOORS DOES NOT | | APPEAR TO INDICATE RAILINGS ON BOTH SIDES BUT ALSO NO | | CENTER RAILING. | | | | PER NFPA 101, CH 7 MEANS OF EGRESS | | | | 7.2.2.4 GUARDS AND HANDRAILS. | | 7.2.2.4.1 HANDRAILS. | | 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON | | BOTH SIDES, | | UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 OR | | 7.2.2.4.1.6. | | 7.2.2.4.1.2 IN ADDITION TO THE HANDRAILS REQUIRED AT | | THE SIDES OF | | STAIRS BY 7.2.2.4.1.1, BOTH OF THE FOLLOWING PROVISIONS | | SHALL APPLY: | | (1) FOR NEW STAIRS, HANDRAILS SHALL BE PROVIDED WITHIN | | 30 IN. (760 | | MM) OF ALL PORTIONS OF THE REQUIRED EGRESS WIDTH. | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] |
|